| EM 300 ERS, FOR ET 200 X, ELECTRONIC REVERSING STARTER, SETTING RANGE 0.6...2.18A, AC-3, 0.18...0.75KW/400V, WITH BRAKE CONTACT, DC 500V/1A, W. 9-POLE POWER CONNECTION, MIN. DISCONNECTION TIME 1S |
|
General details: |
Design of the product | | reversing starter |
Product function / bus-communication | | Yes |
Protocol / will be supported / AS interface protocol | | No |
Protocol / will be supported / PROFIBUS DP protocol | | Yes |
Product component / outlet for enine brake | | Yes |
Item designation / according to DIN EN 61346-2 | | Q |
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 | | A |
Depth | mm | 134 |
Height | mm | 270 |
Width | mm | 140 |
|
Control circuit: |
type of voltage | | DC |
Control supply voltage | | |
- for DC / rated value / minimum
| V | 20.4 |
- for DC / rated value / maximum
| V | 28.8 |
|
Main circuit: |
Design of the short-circuit protection | | fuse |
Type of the motor protection | | solid-state |
Design of the switching contact | | solid-state |
Operating voltage / rated value | | |
| V | 400 |
| V | 500 |
Service power | | |
- at AC-3 / at 400 V / rated value
| kW | 0.8 |
- for three-phase servomotors / at 400 V / at 50 Hz / for AC three-phase
| | |
| kW | 0.18 |
| kW | 0.8 |
Adjustable response current / of the current-dependent overload release | | |
| A | 0.6 |
| A | 2.18 |
Breaking capacity limit short-circuit current (lcu) / at 400 V / rated value | A | 100 |
|
Connection type: |
Design of the electrical connection / for main current circuit | | tab terminals |
|
Ambient conditions: |
Protection class IP | | IP65 |
Ambient temperature | | |
| °C | 0… 55 |
|
Certificates/approvals: | | |
General Product Approval | Test Certificates | Shipping Approval | ROSTEST | Manufacturer | | |
| |
|
last change: | Feb 6, 2012 |