| LOGO! 12/24RC,LOGIC MOD.,DISPL. PU/I/O: 12/24V DC/RELAY + CLOCK 8 DI/4 DO; OF WHICH 2AI 0 -10V MOUNTING ON DIN RAIL STANDARD N |
|
Supply voltage |
12 V DC | Yes |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V; 10.8 V DC with 12 V DC input voltage |
permissible range, upper limit (DC) | 28.8 V; 15.6 V DC at input voltage 12 V DC |
Power losses |
Power loss, max. | 1.6 W; 0.1 to 1.2 W (DC 12 V); 0.2 to 1.6 W (DC 24 V) |
Time of day |
Time switching clocks |
Number | 1; integrated |
Digital inputs |
Number/binary inputs | 8; Of which 2 can be used in analog mode (0 to 10 V) |
Input voltage |
Rated value, DC | 12 V; 12/24 V DC |
for signal "0" | max. 5 V |
for signal "1" | min. 8 V |
Input current |
for signal "1", typ. | 1.5 mA; 1.5 mA at DC 12 V; 2.5 mA at DC 24 V |
Digital outputs |
Number/binary outputs | 4; Relay |
Functionality/short-circuit strength | No; external fusing necessary (max. 16 A) |
Switching frequency |
with resistive load, max. | 2 Hz |
with inductive load, max. | 0.5 Hz |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. | 3 A |
Switching frequency/contacts/at ohmic load/maximum | 10 A |
Analog inputs |
Number of analog inputs | 2 |
Input ranges |
Voltage | Yes |
Input ranges (rated values), voltages |
0 to +10 V | Yes |
Ambient conditions |
Operating temperature |
Min. | 0 °C |
max. | 55 °C |
Storage/transport temperature |
Min. | -20 °C |
max. | 70 °C |
Connection method |
Connecting cables/cross sections | 2 x 1.5 mm2 1-wire; 1 x 0.5 to 2.5 mm2 1-wire; 1 x 0.5 to 2. 5 mm2 finely stranded with end sleeve |
Dimensions |
Width | 72 mm |
Height | 90 mm |
Depth | 55 mm |
Status | Mar 12, 2012 |