| SITOP MODULAR PLUS 20 STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/20 A VERSION WITH COATED PCB |
Technical specifications | |
Product | SITOP modular plus |
Power supply, type | 24 V/20 A |
Input | |
Input | 1-phase and 2-phase AC |
Supply voltage / 1 / at AC / nominal value | 120 V |
Supply voltage / 2 / at AC / nominal value | 230 V |
Voltage range | |
| Set by means of wire jumper on the device; starting from Vin > 93/183 V |
Input voltage / 1 / at AC | 85… 132 V |
Input voltage / 2 / at AC | 176… 264 V |
Wide-range input | No |
Overvoltage resistance | 2.3 × Vin rated, 1.3 ms |
Mains buffering at Iout rated, min. | 20 ms |
Mains buffering | at Vin = 230 V |
Rated line frequency | 50/ 60 Hz |
Rated line range | 47... 63 Hz |
Input current / at nominal level of the input voltage 120 V | 7.7 A |
Input current / at nominal level of the input voltage 230 V | 3.5 A |
Switch-on current limiting (+25 °C), max. | 60 A |
Inrush current A²s | 9.9 A²·s |
Built-in incoming fuse | Yes |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker at 1-phase operation: 10 A, characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V) |
Output | |
Output | controlled, isolated DC voltage |
Rated voltage | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.1 % |
Residual ripple peak-peak, max. | 100 mV |
Residual ripple peak-peak, typ. | 30 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 60 mV |
Adjustment range | 24… 28.8 V |
Product feature / output voltage adjustable | Yes |
Output voltage setting | via potentiometer |
Status display | Green LED for 24 V OK |
Signaling | via signaling module (6EP1961-3BA10) |
On/off behavior | Overshoot of Vout approx. 3 % |
Startup delay, max. | 0.1 s |
Voltage rise, typ. | 50 ms |
Rated current value Iout rated | 20 A |
Current range | 0… 20 A |
| > 60 °C Derating |
delivered active power / typ. | 480 W |
constant overload current / at short-circuit during run-up / typical | 23 A |
short-term overload current / at short-circuit during operation / typical | 60 A |
Duration of overloading ability for excess current / on short-circuiting during the operational phase | 25 ms |
Parallel switching for enhanced performance | Yes |
| switchable characteristic |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency | |
Efficiency at Vout rated, Iout rated, approx. | 89 % |
Power loss at Vout rated, Iout rated, approx. | 59 W |
Closed-loop control | |
Dynamic mains compensation (Vin rated ±15 %), max. | 1 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 2 % |
Load step setting time 50 to 100%, typ. | 2 ms |
Load step setting time 100 to 50%, typ. | 2 ms |
Setting time / maximum | 5 ms |
Protection and monitoring | |
Output overvoltage protection | < 35 V |
Current limitation, typ. | 23 A |
Characteristic feature of the output / short-circuit protected | Yes |
Short-circuit protection | Alternatively, constant current characteristic approx. 23 A or latching shutdown |
Enduring short circuit current / Effective level / typical | 23 A |
Overload/short-circuit indicator | LED yellow for "overload", LED red for "latching shutdown" |
Safety | |
Primary/secondary isolation | Yes |
Potential separation | Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class | Class I |
stray current / maximum | Назад в раздел
|