SITOP MODULAR PLUS 20 STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/20 A VERSION WITH COATED PCB

Артикул: 6EP1336-3BA00-8AA0
Производитель: Siemens


Наименование продукта
SITOP MODULAR PLUS 20 STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/20 A VERSION WITH COATED PCB
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2008-08-15
SITOP MODULAR PLUS 20 STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/20 A VERSION WITH COATED PCB
Technical specifications
Product SITOP modular plus
Power supply, type 24 V/20 A
Input
Input 1-phase and 2-phase AC
Supply voltage / 1 / at AC / nominal value 120 V
Supply voltage / 2 / at AC / nominal value 230 V
Voltage range
  • Note
Set by means of wire jumper on the device; starting from Vin > 93/183 V
Input voltage / 1 / at AC 85 132 V
Input voltage / 2 / at AC 176 264 V
Wide-range input No
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 20 ms
Mains buffering at Vin = 230 V
Rated line frequency 50/ 60 Hz
Rated line range 47... 63 Hz
Input current / at nominal level of the input voltage 120 V 7.7 A
Input current / at nominal level of the input voltage 230 V 3.5 A
Switch-on current limiting (+25 °C), max. 60 A
Inrush current A²s 9.9 A²·s
Built-in incoming fuse Yes
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker at 1-phase operation: 10 A, characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V)
Output
Output controlled, isolated DC voltage
Rated voltage 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.1 %
Residual ripple peak-peak, max. 100 mV
Residual ripple peak-peak, typ. 30 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 200 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 60 mV
Adjustment range 24 28.8 V
Product feature / output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
Signaling via signaling module (6EP1961-3BA10)
On/off behavior Overshoot of Vout approx. 3 %
Startup delay, max. 0.1 s
Voltage rise, typ. 50 ms
Rated current value Iout rated 20 A
Current range 0 20 A
  • Note
> 60 °C Derating
delivered active power / typ. 480 W
constant overload current / at short-circuit during run-up / typical 23 A
short-term overload current / at short-circuit during operation / typical 60 A
Duration of overloading ability for excess current / on short-circuiting during the operational phase 25 ms
Parallel switching for enhanced performance Yes
  • Note
switchable characteristic
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 89 %
Power loss at Vout rated, Iout rated, approx. 59 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 2 %
Load step setting time 50 to 100%, typ. 2 ms
Load step setting time 100 to 50%, typ. 2 ms
Setting time / maximum 5 ms
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 23 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Alternatively, constant current characteristic approx. 23 A or latching shutdown
Enduring short circuit current / Effective level / typical 23 A
Overload/short-circuit indicator LED yellow for "overload", LED red for "latching shutdown"
Safety
Primary/secondary isolation Yes
Potential separation Safety extra low output voltage Vout according to EN 60950-1 and EN 50178
Protection class Class I
stray current / maximum Назад в раздел