| SITOP POWER 0.375 A, DC/DC STABILIZED POWER SUPPLY INPUT: 48-220 V DC OUTPUT: 24 V DC/0.375 A |
Technical specifications | |
Product | SITOP power |
Power supply, type | 24 V/0.375 A |
Input | |
Input | DC voltage |
Supply voltage / at DC | 48… 220 V |
Voltage range | 30… 187 V |
Input voltage / at DC | 30… 264 V |
Wide-range input | Yes |
Overvoltage resistance | - |
Mains buffering at Iout rated, min. | 10 ms |
Mains buffering | at Vin = 220 V |
Input current / at nominal level of the input voltage 48 V | 0.3 A |
Input current / at nominal level of the input voltage 220 V | 0.06 A |
Switch-on current limiting (+25 °C), max. | 35 A |
Duration of current limiting / at 25 °C / typical | 3 ms |
Inrush current A²s | 1.2 A²·s |
Built-in incoming fuse | F 4 A/250 V (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 6 A, characteristic C, suitable for DC |
Output | |
Output | controlled, isolated DC voltage |
Rated voltage | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.1 % |
Static load balancing, approx. | 0.1 % |
Residual ripple peak-peak, max. | 150 mV |
Residual ripple peak-peak, typ. | 50 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 240 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 50 mV |
Product feature / output voltage adjustable | No |
Output voltage setting | - |
Status display | Green LED for 24 V OK |
On/off behavior | No overshoot of Vout (soft start) |
Startup delay, max. | 2.5 s |
Voltage rise, typ. | 90 ms |
Rated current value Iout rated | 0.375 A |
Current range | 0… 0.375 A |
| 0.255 A up to +70 °C |
delivered active power / typ. | 9 W |
short-term overload current / at short-circuit during operation / typical | 2.7 A |
Duration of overloading ability for excess current / on short-circuiting during the operational phase | 200 ms |
Parallel switching for enhanced performance | No |
Efficiency | |
Efficiency at Vout rated, Iout rated, approx. | 66 % |
Power loss at Vout rated, Iout rated, approx. | 4.6 W |
Closed-loop control | |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.3 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 0.4 % |
Load step setting time 50 to 100%, typ. | 2 ms |
Load step setting time 100 to 50%, typ. | 2 ms |
Protection and monitoring | |
Output overvoltage protection | Yes, according to EN 60950 |
Current limitation | 0.41… 0.49 A |
Characteristic feature of the output / short-circuit protected | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Enduring short circuit current / Effective level / maximum | 0.9 A |
Overload/short-circuit indicator | - |
Safety | |
Primary/secondary isolation | Yes |
Potential separation | Safety extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class | Class I |
stray current / maximum | 3.5 mA |
CE mark | Yes |
UL/CSA approval | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289, cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
Explosion protection | - |
FM approval | - |
CB approval | No |
Marine approval | - |
Degree of protection (EN 60529) | IP20 |
EMC | |
Emitted interference | EN 55022 Class B |
Supply harmonics limitation | not applicable |
Noise immunity | EN 61000-6-2 |
Operating data | |