| SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 DI, 120V AC W. 1 POINT COMMO |
|
General information |
Vendor identification (VendorID) | 002AH |
Supply voltage |
24 V DC | Yes |
Reverse polarity protection | Yes |
Input current |
from supply voltage L1, max. | 90 mA |
Power losses |
Power loss, typ. | 5.4 W |
Hardware configuration |
Rack |
Required terminal block | TB 16L AC |
Digital inputs |
Number/binary inputs | 16 |
Input characteristic curve acc. to IEC 61131, Type 2 | Yes |
Number of simultaneously controllable inputs | 16 |
Input voltage |
Rated value, AC | 120 V |
for signal "0" | 0 to 20 V |
for signal "1" | 74 to 132 V |
Input current |
for signal "0", min. | 0 mA |
for signal "0", max. (permissible quiescent current) | 4 mA |
for signal "1", typ. | 9 mA; 9 to 27 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", min. | 2 ms |
at "0" to "1", max. | 14 ms |
at "1" to "0", min. | 6 ms |
at "1" to "0", max. | 25 µs |
Cable length |
Cable length unshielded, max. | 600 m |
Cable length for NAMUR input, shielded, max. | 1000 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 1.5 Mbit/s; 9.6 / 19.2 / 93.75 / 187.5 / 500 Kbit/s; 1.5 / 3 / 6 Mbit/s |
FREECE capability | Yes |
Direct data exchange (slave-to-slave communication) | Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
Alarms | No |
Diagnostic messages |
Diagnostic functions | Yes |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Status indicator digital output (green) | Yes |
Status indicator digital input (green) | Yes |
Monitoring 24 V voltage supply ON (green) | Yes |
Galvanic isolation |
between PROFIBUS DP and all other circuit components | Yes |
Galvanic isolation digital inputs |
between the channels | Yes |
between the channels and PROFIBUS DP | Yes |
Isolation |
Isolation checked with | 1500 V AC |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 5 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width | 191 mm |
Height | 61 mm |
Depth | 85.5 mm |
Weight |
Weight, approx. | 341 g |
Status | Mar 12, 2012 |