| SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DI HIGH FEATURE 24V DC, 15 MM WIDTH WITH PARAM. F. INPUT DELAY DIAGNOSIS F. ENCODER SHORT- CIRCUIT W. LED SF (GROUP FAULT) 5 PIECES PER PACKAGING UNIT |
|
Supply voltage |
24 V DC | Yes; From power module |
Reverse polarity protection | Yes |
Input current |
from backplane bus 3.3 V DC, max. | 10 mA |
from supply voltage L+, max. | Dependent on encoder |
Encoder supply |
Output voltage | min. L+ (-0.5 V), under load |
Output current, rated value | 500 mA |
Output current, permissible range | 0 to 500 mA |
Output current |
Short-circuit protection | Yes; Electronic |
Power losses |
Power loss, typ. | 0.4 W |
Address area |
Address space per module |
with packing | 2 bit |
without packing | 1 byte |
Digital inputs |
Number/binary inputs | 2 |
Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
Input voltage |
Rated value, DC | 24 V |
for signal "0" | -30 to +5 V |
for signal "1" | 11 to 30 V |
Input current |
for signal "1", typ. | 8 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | Yes; 0.1 / 0.5 / 3 / 15 ms |
at "0" to "1", min. | 0.05 ms |
at "0" to "1", max. | 15.15 ms |
at "1" to "0", min. | 0.05 ms |
at "1" to "0", max. | 15.15 ms |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
Permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Alarms |
Hardware interrupt | Yes; Parameterizable |
Diagnostic messages |
Diagnostic information readable | Yes |
Short circuit | Yes; Short-circuit of outputs to ground; module by module |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital input (green) | Yes |
Parameter |
Diagnosis: short circuit | Disable / enable |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 35 g |
Status | Mar 12, 2012 |