| SIMATIC DP, 5 ELECTRON. MODULES ET 200S: 4DI UC 24V...48V, 15 MM WIDTH, WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT |
|
Supply voltage |
24 V DC | Yes; From power module |
permissible range, lower limit (DC) | 24 V |
permissible range, upper limit (DC) | 48 V |
24 V AC | Yes |
permissible range, lower limit (AC) | 24 V |
permissible range, upper limit (AC) | 48 V |
Reverse polarity protection | Yes; AC or DC automatic |
Input current |
from backplane bus 3.3 V DC, max. | 10 mA |
from supply voltage L+, max. | Dependent on encoder |
Encoder supply |
Output voltage | min. L+ (-0.5 V), under load |
Output current, rated value | 500 mA |
Output current, permissible range | 0 to 500 mA |
Output current |
Short-circuit protection | Yes; per module |
Power losses |
Power loss, typ. | 0.7 W |
Address area |
Address space per module |
with packing | 4 bit |
without packing | 1 byte |
Digital inputs |
Number/binary inputs | 4 |
Input characteristic curve acc. to IEC 61131, Type 1 | Yes |
Input voltage |
Type of input voltage | AC/DC |
Rated value, UC | 24 V; 24 to 48 V UC |
for signal "0" | -6 to 6 V DC, 0 to 5 V AC |
for signal "1" | -15 to -57.6 V DC; -15 to 57.6 V DC; 15 to 48 V AC |
Frequency range | 47 to 63 Hz |
Input current |
for signal "1", typ. | 10 mA; 4 to 10 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. | 15 ms |
at "1" to "0", max. | 15 ms |
Encoder connection |
Fixed current limitation for wire break monitoring, min. | 18 kΩ; Rated voltage 24 V (15 V to 35 V); rated voltage 48 V (30 V to 60 V): 39 kohms |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
Permissible quiescent current (2-wire sensor), max. | 2 mA; (0.5 to 2 mA), a minimum load current is necessary for wire break diagnostics. |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Diagnostic messages |
Diagnostic functions | Yes; Parameterizable |
Diagnostics indication LED |
Group error SF (red) | Yes |
Status indicator digital input (green) | Yes; per channel |
Galvanic isolation |
Galvanic isolation digital inputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
Isolation checked with | 2500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 35 g |
Status | Mar 12, 2012 |