| SIMATIC DP, ELECT. SUBMODULE DIGITAL, FOR ET200B, W=235MM 16RO, 120/230V AC,2/4A APPLICABLE ON TB6/AC RELAY SWITCHING VOLTAGE 230V AC |
|
Hardware configuration |
Rack |
Required terminal block | TB6/AC |
Digital outputs |
Number/binary outputs | 16; 4 high and 12 low current relays |
Functionality/short-circuit strength | No |
Output voltage |
Rated value (AC) | 120/230 V AC |
Rated value (DC) | 61 to 150 V DC |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 2 Hz |
Relay outputs |
Switching capacity of contacts |
Switching frequency/contacts/at ohmic load/maximum | 4 A; 4 A (2 ports); 2 A (12 ports) |
Cable length |
Cable length unshielded, max. | 600 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Galvanic isolation |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs | Yes |
between the channels, in groups of | 1 |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Status | Mar 5, 2012 |