| SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 16 DO, 24V DC/0.5A |
|
General information |
Vendor identification (VendorID) | 0016h |
Supply voltage |
24 V DC | Yes |
Reverse polarity protection | Yes |
Mains buffering |
Mains buffering, min. | 20 ms |
Load voltage 2L+ |
Rated value (DC) | 24 V; 1L+, 2L+, 3L+ |
Input current |
from load voltage L1 (without load), max. | 50 mA; Per load group (L1+ or L2+ / L3+) |
from supply voltage L+, max. | 70 mA; L4+ / L5+ |
Power losses |
Power loss, typ. | 5 W |
Hardware configuration |
Rack |
Required terminal block | TB 16L |
Digital outputs |
Number/binary outputs | 16 |
Functionality/short-circuit strength | Yes; Electronic |
Response threshold, typ. | 0.7 A |
Limitation of inductive shutdown voltage to | Typ. (L1+ or L2+ / L3+) -55 V |
Lamp load, max. | 5 W |
Controlling a digital input | Yes |
Load resistance range |
lower limit | 41 Ω |
upper limit | 28000 Ω |
Output voltage |
Rated value (DC) | 24 V |
for signal "1", min. | Ua - 3 V |
Output current |
for signal "1" rated value | 0.5 A |
for signal "1" permissible range for 0 to 60 °C, max. | 0.5 A |
for signal "0" residual current, max. | 1 mA |
Output delay with resistive load |
0 to "1", max. | 50 ms |
1 to "0", max. | 200 ms |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes; only outputs of the same group |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 8 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 60 °C, max. | 4 A |
all other mounting positions |
up to 40 °C, max. | 2 A |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 1.5 Mbit/s |
SYNC capability | Yes |
Direct data exchange (slave-to-slave communication) | Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC) |
Communication functions |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
Alarms | No |
Diagnostic messages |
Diagnostic functions | Yes |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Status indicator digital output (green) | Yes |
Status indicator digital input (green) | Yes |
Monitoring 24 V voltage supply ON (green) | Yes |
Galvanic isolation |
between PROFIBUS DP and all other circuit components | Yes |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and PROFIBUS DP | Yes; Optocoupler |
Isolation |
Isolation checked with | 500 V DC |
Ambient conditions |
Operating temperature |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity |
Operation, min. | 5 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection |
IP20 | Yes |
Connection method |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width | 145 mm |
Height | 60 mm |
Depth | 60.5 mm |
Weight |
Weight, approx. | 130 g |