| SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO 24...230V AC, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT |
|
Supply voltage |
Reverse voltage protection | Yes; when using the same load voltage as on the power module |
Load voltage L+ |
Reverse polarity protection | Yes |
Load voltage L1 |
Rated value (AC) | 24.23 V; From power module |
permissible range, lower limit (AC) | 24 V |
permissible range, upper limit (AC) | 230 V |
permissible frequency range, lower limit | 47 Hz |
permissible frequency range, upper limit | 63 Hz |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from load voltage L1 (without load), max. | 15 mA; Per channel |
from backplane bus 3.3 V DC, max. | 18 mA |
Power losses |
Power loss, typ. | 4 W |
Address area |
Address space per module |
with packing | 2 bit |
without packing | 1 byte |
Digital outputs |
Number/binary outputs | 2 |
Size of motor starter, max. | up to 40 °C size acc. to NEMA: 5; up to 60 °C size acc. to NEMA: 4 |
Functionality/short-circuit strength | Yes; via fuse in power module |
Limitation of inductive shutdown voltage to | -55 to -60 V |
Lamp load, max. | 100 W |
Zero-crossing switch | Yes; Max. 25 V |
Controlling a digital input | Yes; possible |
Output voltage |
for signal "1", min. | L+ (-1.5 V) |
Output current |
for signal "1" rated value | 2 A |
for signal "1" permissible range for 0 to 60 °C, min. | 0.1 mA |
for signal "1" permissible range for 0 to 60 °C, max. | 2.2 A |
for signal "0" residual current, max. | 3 mA |
Output delay with resistive load |
0 to "1", max. | 15 ms |
1 to "0", max. | 15 ms |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes; per module |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 40 °C, max. | 2 A |
up to 50 °C, max. | 1.5 A |
up to 60 °C, max. | 1 A |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes; 0/1 |
Diagnostic messages |
Diagnostic functions | No |
Diagnostics indication LED |
Status indicator digital output (green) | Yes |
Parameter |
Remark | 3 bytes |
Behavior on CPU/Master STOP, channel-wise | Substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels | No |
between the channels and the backplane bus | Yes |
Isolation |
Isolation checked with | 2500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 37 g |
Status | Mar 12, 2012 |