SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 17,4V/27MA, "H"-SHUT DOWN

Артикул: 6ES7132-7RD11-0AB0
Производитель: Siemens


Наименование продукта
SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 17,4V/27MA, "H"-SHUT DOWN
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2006-07-01
Manuals weitere>>
Устройство децентрализованной периферии ET 200 iSP  2007-03-14
SIMATIC DP, ELECT. SUBMODULE FOR ET 200ISP, 4 DO, DC 17,4V/27MA, "H"-SHUT DOWN
Input current
from load voltage L+ (without load), max. 300 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 2.1 W
Address area
Address space per module
without packing 2 byte
Digital outputs
Number/binary outputs 4; additionally 1 intrinsically-safe input for H shutdown
Functionality/short-circuit strength Yes
No-load voltage Uao (DC) 17.4 V
Internal resistor Ri 150 Ω
Trend key points E
Voltage Ue (DC) 13.2 V
Current Ie 27 mA
Output current
for signal "1" rated value 0.03 A
Output delay with resistive load
0 to "1", max. 2 ms
1 to "0", max. 1.5 ms
Parallel switching of 2 outputs
for increased power Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 2 Hz
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 500 m
Interrupts/diagnostics/status information
Alarms
Alarms No
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Wire break Yes
Short circuit Yes
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Parameter
Remark 14 bytes
Diagnosis: wire break Yes
Diagnosis: short circuit Yes
Behavior on CPU/Master STOP, channel-wise Yes
Ex(i) characteristics
Max. values of output circuits (per channel)
Ta (permissible ambient temperature), max. 70 °C
Standards, approvals, certificates
CE mark Yes
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
Type of protection acc. to KEMA Not relevant
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weight
Weight, approx. 255 g
Status Mar 12, 2012

Назад в раздел