| SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, MICRO MEMORY CARD REQUIRED |
|
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Inrush current, max. | 11 A |
from supply voltage L+, max. | 900 mA |
Power losses |
Power loss, typ. | 10 W |
Memory |
Work memory |
integrated | 32 kbyte; For program and data |
expandable | No |
Load memory |
expandable FEPROM | Yes; with Micro Memory Card (MMC) |
expandable FEPROM, max. | 4 Mbyte |
Backup |
present | Yes; Guaranteed by MMC (maintenance-free) |
without battery | Yes; Program and data |
CPU processing times |
for bit operations, min. | 0.1 µs |
for bit operations, max. | 0.2 µs |
for word operations, min. | 0.5 µs |
for fixed point arithmetic, min. | 1 µs |
for floating point arithmetic, min. | 15 µs |
CPU-blocks |
DB |
Number, max. | 127; DB 0 reserved |
Size, max. | 16 kbyte |
FB |
Number, max. | 128 |
Size, max. | 16 kbyte |
FC |
Number, max. | 128 |
Size, max. | 16 kbyte |
OB |
Size, max. | 16 kbyte |
Number of time alarm OBs | 1 |
Number of delay alarm OBs | 1 |
Number of time interrupt OBs | 1 |
Number of process alarm OBs | 1 |
Nesting depth |
per priority class | 8 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 256 |
of which retentive without battery |
adjustable | Yes |
lower limit | 0 |
upper limit | 256 |
Counting range |
lower limit | 1 |
upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 256 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 256 |
Time range |
lower limit | 10 ms |
upper limit | 9990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
Address area |
I/O address area |
Inputs | 1 kbyte |
Outputs | 1 kbyte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Digital channels |
Inputs | 992 |
Outputs | 992 |
Analog channels |
Inputs | 248 |
Outputs | 124 |
Hardware configuration |
Modules per rack, max. | 31 |
Expansion devices, max. | 3 |
Number of DP masters |
integrated | 1 |
via CP | 1 |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, point-to-point | 4 |
CP, LAN | 2 |
Time of day |
Clock |
Hardware clock (real-time clock) | Yes |
battery-backed and synchronizable | Yes |
Operating hours counter |
Number | 1 |
Clock synchronization |
supported | Yes |
Digital inputs |
Number/binary inputs | 16 |
Input voltage |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 15 to 30 V |
Input current |
for signal "1", typ. | 8 mA; Min. 2 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable | Yes; 0.1 / 0.3 / 3 / 15 ms |
for counter/technological functions |
at "0" to "1", max. | 8 µs |
Cable length |
Cable length, shielded, max. | 1000 m; 100 m for technological functions |
Cable length unshielded, max. | 600 m |
Digital outputs |
Number/binary outputs | 16 |
Functionality/short-circuit strength | Yes; Clocked electronically |
Limitation of inductive shutdown voltage to | L+ (-48 V) |
Output voltage |
for signal "1", min. | L+ (-0.8 V) |
Output current |
for signal "1" permissible range for 0 to 40 °C, max. |
|