| SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 DIO / 4 DO DC 24V, 0.5A MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4CB50-0AA0 MUST BE ORDERED SEPERATELY |
|
Supply voltage |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; Against destruction; encoder power supply outputs applied with reversed polarity |
Load voltage 2L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; against destruction; load increasing |
Input current |
from load voltage 1L+ (unswitched voltage) | 20 mA |
from load voltage 2L+, max. | 20 mA |
Encoder supply |
Number of outputs | 4 |
Output current, rated value | 1 A; per module, electronic |
24 V encoder supply |
Short-circuit protection | Yes; per module, electronic |
Power losses |
Power loss, typ. | 3 W |
Digital inputs |
Number/binary inputs | 4; 4 DIOs can be parameterized |
Input characteristic curve acc. to IEC 61131, Type 3 | Yes |
Number of simultaneously controllable inputs |
all mounting positions |
up to 60 °C, max. | 4; Up to 55 °C |
Input voltage |
Rated value, DC | 24 V |
for signal "0" | -3 to +5 V |
for signal "1" | 11 to 30 V |
Input current |
for signal "0", max. (permissible quiescent current) | 1.5 mA |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
at "0" to "1", max. | 4.8 ms |
at "1" to "0", max. | 4.8 ms |
Cable length |
Cable length unshielded, max. | 30 m |
Digital outputs |
Number/binary outputs | 8; 4 DO fixed, 4 DIO parameterizable |
In groups of | 2; 2 load groups for 4 outputs each |
Functionality/short-circuit strength | Yes; per channel, electronic |
Response threshold, typ. | 0.7 A |
Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Controlling a digital input | Yes |
Output current |
for signal "1" rated value | 0.5 A |
for signal "0" residual current, max. | 0.5 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
up to 55 °C, max. | 2 A |
Cable length |
Cable length unshielded, max. | 30 m |
Interrupts/diagnostics/status information |
Status indicator | Yes; Green LED |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic functions | Yes |
Diagnostic information readable | Yes |
Short circuit | Yes; Short-circuit of outputs to ground; module by module |
Short circuit encoder supply | Yes; per module |
Group error | Yes |
Galvanic isolation |
between the load voltages | Yes |
between load voltage and all other switching components | Yes |
Galvanic isolation digital inputs |
between the channels | No |
Permissible potential difference |
between different circuits | 75 VDC / 60 VAC |
Isolation |
tested with |
24 V DC circuits | 500 V |
Dimensions |
Width | 45 mm |
Height | 130 mm |
Depth | 35 mm |
Weight |
Weight | 140 g |
Status | Mar 12, 2012 |