| SIPLUS HMI TP177B 4" COLOR PN/D -10 ... +60 DEGREES C WITH CONFORMAL COATING BASED ON 6AV6642-0BD01-3AX0 . TFT 256 COLOR-16:9-DISPLAY, MPI-/PROFIBUS-DP - PROTOCOL RS485-/RS422-/USB - INTERFACE ETHERNET10/100 INTERFACE PRINTER - INTERFACE SLOT FOR MM-CARD CONFIGURABLE WITH WINCC FLEXIBLE 2008 |
|
General information |
Customer-specific configuration | Yes |
Display |
Design of display | TFT |
Screen diagonal | 4.3 in |
Size | 4.3" (95 mm x 53 mm) |
Display type | TFT, 256 Farben |
Color type | Colors |
Resolution (pixels) |
Horizontal image resolution | 480 |
Vertical image resolution | 272 |
Resolution (WxH in pixel) | 480 x 272 |
Backlighting |
MTBF backlighting (at 25 °C) | Approx. 30,000 hours |
Control elements |
Control elements | Membrane keyboard |
Operating mode |
Operating options | Keys and Touch |
Function keys, programmable | 4 function keys |
Connection for mouse/keyboard/barcode reader | USB / USB / USB |
Keyboard fonts |
freely inscribable membrane keys | Yes |
Number of function keys with LEDs | 0 |
Multi-key operation | Yes |
System keys | No |
Numeric/alphabetical input | Yes (on-screen keyboard) / Yes (on-screen keyboard) |
hexadecimal keyboard | Yes; Onscreen keyboard |
Touch operation |
Touch screen | Analog, resistive |
Touch screen (analog/resistive) | Yes |
Supply voltage |
Supply voltage | 24 V DC |
Input current |
Rated current | 0.2 A |
Inrush current A²s | 0.1 A²·s |
Processor |
Processor | RISC 32-bit, 266 MHz |
Processor type | RISC 32-bit |
Memory |
Type | Flash / RAM |
Usable memory for user data | 2048 KB usable memory for user data |
Main memory | |
Capacity of main memory, maximum | 64 Mbyte |
Time of day |
Clock |
Type | Hardware clock, synchronizable, no battery backup |
Interfaces |
Interfaces | RS232 optional, 1 x RS422, 1 x RS485, 1 x Ethernet (RJ45) (max. 12 Mbit/s) |
Number of RS 485 interfaces | 1 |
Transmission rate, max. | 12 Mbit/s |
USB port | 1 x USB |
PC card slot | No |
CF card slot | No |
Multimedia card/SD card slot | combined |
Special interfaces | No |
Industrial Ethernet |
Industrial Ethernet interface | 1 x Ethernet (RJ45) |
Industrial Ethernet status LED | 1 |
Protocols |
Protocols (Ethernet) |
TCP/IP | Yes |
Protocols (terminal link) |
Sm@rtAccess | Yes |
Further protocols |
PROFIBUS | Yes |
MPI | Yes |
Ambient conditions |
Mounting position | vertical |
maximum permissible angle of inclination without external ventilation | +/- 35 ° |
Storage/transport temperature |
Transport, storage | -20 °C to +60 °C |
Extended ambient conditions |
Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity |
with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Degree and class of protection |
Front | IP65, NEMA 4, NEMA 4x, NEMA 12 (when installed) |
Type of protection | IP20 |
IP (at the front) | IP65 |
NEMA | NEMA 4, NEMA 4x, NEMA 12 |
Rear | IP20 |
Standards, approvals, certificates |
Certifications | CE |
FM Class I Div. 2 | No |
Gost-R | Yes |
Suitable for safety functions | No |
Use in hazardous areas |
EX zone 2 | No |
EX zone 22 | No |
Operating systems |
Operating system | Windows CE (Version 5) |
Configuration |
Message indicator | Yes |
With alarm logging system (incl. buffer and acknowledgment) | Yes |
Process value display (output) | Yes |
Process value default (input) possible | Yes |
Recipe administration | Yes |
Configuration software |
Configuration tool | WinCC flexible Compact Version 2008 or higher (to be ordered separately) |
2nd configuration kit | WinCC flexible Compact |
Version | Version 2008 |
Configuration tool | WinCC flexible |
Type | Compact |
Languages |
Online languages |
Number of online/runtime languages | 5 |
Languages |
Languages per project | 32 |
Functionality under WinCC flexible |
Libraries | Yes |
Task planner | Yes |
Help system | Yes |
Number of characters per info text | 70 |
With alarm logging system (incl. buffer and acknowledgment) |
Number of alarm classes | 32 |
Number of messages | 2000 |
Bit messages | Yes |
Analog messages | Yes |
Number of bit messages | 2000 |
Number of analog messages | 2000 |
Telegram message procedure Alarm S | Yes |
System messages HMI | Yes |
System messages PLC | Yes |
System messages, other (SIMATIC S7, Sinumerik, Simotion,..) | No |
Message length (in characters) | 80 |
|