SIMATIC TOUCH PANEL TP 177A 5,7" BLUE MODE STN-DISPLAY, MPI/PROFIBUS-DP INTERFACE, CONFIGURABLE WINCC FLEXIBLE 2004 COMPACT HSP UPWARDS; CONTAINS OPEN-SOURCE-SW, WHICH IS PROVIDED FREE OF CHARGE. FOR DETAILS SEE ENCLOSED CD

Артикул: 6AV6642-0AA11-0AX1
Производитель: Siemens


Наименование продукта
SIMATIC TOUCH PANEL TP 177A 5,7" BLUE MODE STN-DISPLAY, MPI/PROFIBUS-DP INTERFACE, CONFIGURABLE WINCC FLEXIBLE 2004 COMPACT HSP UPWARDS; CONTAINS OPEN-SOURCE-SW, WHICH IS PROVIDED FREE OF CHARGE. FOR DETAILS SEE ENCLOSED CD
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-06-01 2008-07-11 2008-07-11
SIMATIC TOUCH PANEL TP 177A 5,7" BLUE MODE STN-DISPLAY, MPI/PROFIBUS-DP INTERFACE, CONFIGURABLE WINCC FLEXIBLE 2004 COMPACT HSP UPWARDS; CONTAINS OPEN-SOURCE-SW, WHICH IS PROVIDED FREE OF CHARGE. FOR DETAILS SEE ENCLOSED CD
Display
Design of display STN
Screen diagonal 5.7 in
Size 5.7"
Display type STN, 4 blue levels
Color type Blue levels
Resolution (pixels)
Horizontal image resolution 320
Vertical image resolution 240
Resolution (WxH in pixel) 320 x 240
Backlighting
MTBF backlighting (at 25 °C) about 50000 hours
Control elements
Control elements Touch screen
Operating mode
Operating options Touch
Connection for mouse/keyboard/barcode reader - / - / -
Keyboard fonts
Numeric/alphabetical input Yes / Yes
hexadecimal keyboard Yes
Multi-key operation No
Touch operation
Touch screen Analog, resistive
Supply voltage
Supply voltage 24 V DC
Input current
Rated current 0.24 A
Inrush current A²s 0.5 A²·s
Power
Power 6 W
Processor
Processor ARM
Processor type ARM
Memory
Type Flash / RAM
Usable memory for user data 512 KB usable memory for user data
Type of output
Info LED No
Power LED No
Error LED No
Time of day
Clock
Type Software clock, no battery backup
Interfaces
Interfaces 1 x RS422, 1 x RS485 (max. 1.5 Mbit/s)
Number of RS 485 interfaces 1
Transmission rate, max. 1.5 Mbit/s
USB port No
PC card slot No
CF card slot No
Multi Media Card slot No
Special interfaces No
Industrial Ethernet
Industrial Ethernet interface No
Ambient conditions
Mounting position vertical
maximum permissible angle of inclination without external ventilation +/- 35 °
Storage/transport temperature
Transport, storage -20 °C to +60 °C
Relative humidity
max. relative humidity 90 %
Degree and class of protection
Front IP65, NEMA 4x (when installed)
Type of protection IP20
IP (at the front) IP65
NEMA NEMA 4X
Rear IP20
Standards, approvals, certificates
Certifications CE, GL, ABS, BV, DNV, LRS, FM Class I Div. 2, UL, CSA, cULus, C-TICK, NEMA 4x
FM Class I Div. 2 Yes
GL Yes
ABS Yes
BV Yes
DNV Yes
LRS Yes
Class NK Yes
PRS No
Gost-R No
Use in hazardous areas
EX zone 2 No
EX zone 22 No
Operating systems
Operating system LINUX
Configuration
Configuration software
Configuration tool WinCC flexible Compact Version 2004 SP1 or higher (to be ordered separately)
2nd configuration kit WinCC flexible Compact
Version Version 2004 SP 1
Configuration tool WinCC flexible
Type Compact
Languages
Online languages
Number of online/runtime languages 5
Languages
Languages per project 32
Functionality under WinCC flexible
Libraries Yes
Number of Visual Basic Scripts Not possible
Debugging in the simulator No
Task planner Yes
Help system Yes
Number of characters per info text 320
Number of tooltips 0
With alarm logging system (incl. buffer and acknowledgment)
Number of alarm classes 32
Number of messages 1000
Bit messages Yes
Analog messages Yes
Number of bit messages 1000
Number of analog messages 0
Telegram message procedure Alarm S No
System messages HMI Yes
System messages PLC Yes
System messages, other (SIMATIC S7, Sinumerik, Simotion,..) No
Message length (in characters) 80
Lines 1
Number of process values per message 8
Acknowledgment groups Yes
Message indicator Yes
Acoustic feedback No
First/last value Yes
Recipes
Recipes 5
Data records per recipe 20
Entries per data record 20
Recipe memory 32 KB integrated Flash
Variables
Number of variables per device 500
Number of variables per screen 30
Limit values Yes
Multiplexing Yes
Structs No
Images
Number of configurable images 250
Permanent window/default Yes
Start screen configurable Yes
Image selection by PLC Yes
Image number in the PLC Yes
Image objects
Text objects 1,000 text elements
Fields per image 30
Index of screen context No
Return

Назад в раздел