CONTACTOR, AC-3, 7.5KW/400V, 1NO+1NC, AC(50-60HZ)/DC ACTUAT. , UC 200...280V, 3-POLE, SZ S0 SCREW TERMINAL

Артикул: 3RT2025-1NP30
Производитель: Siemens


Наименование продукта
CONTACTOR, AC-3, 7.5KW/400V, 1NO+1NC, AC(50-60HZ)/DC ACTUAT. , UC 200...280V, 3-POLE, SZ S0 SCREW TERMINAL
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
    Версия от 2011-11-12
 
CONTACTOR, AC-3, 7.5KW/400V, 1NO+1NC, AC(40-60HZ)/DC ACTUAT. , UC 200...280V, 3-POLE, SZ S0 SCREW TERMINAL
 
General technical data:
Product brand name   SIRIUS
Size of the contactor   S0
Product extension / auxiliary switch   Yes
Protection class IP / on the front   IP20
Protection against electrical shock   finger-safe
Degree of pollution   3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature / during storage °C -55 80
Ambient temperature / during operating °C -25 60
Shock resistance    
  • at rectangular impulse
   
  • at AC
  7,5g / 5 ms, 4,7g / 10 ms
  • at DC
  10g / 5 ms, 7,5g / 10 ms
  • at sine pulse
   
  • at AC
  11,8g / 5 ms, 7,4g / 10 ms
  • at DC
  15g / 5 ms, 10g / 10 ms
Impulse voltage resistance / rated value kV 6
Insulation voltage / rated value V 690
Mechanical operating cycles as operating time    
  • of the contactor / typical
  10,000,000
  • of the contactor with added auxiliary switch block / typical
  10,000,000
  • of the contactor with added electronics-compatible auxiliary switch block / typical
  5,000,000
 
Main circuit:
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating current    
  • at AC-1 / at 400 V
   
  • at 40 °C ambient temperature / rated value
A 40
  • at 60 °C ambient temperature / rated value
A 35
  • at AC-2 / at 400 V / rated value
A 17
  • at AC-3 / at 400 V / rated value
A 17
  • at AC-4 / at 400 V / rated value
A 15.5
Operating current    
  • with 1 current path / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 4.5
  • with 2 current paths in series / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
  • with 3 current paths in series / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
  • with 1 current path / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 2.5
  • with 2 current paths in series / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 15
  • with 3 current paths in series / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
Service power    
  • at AC-2 / at 400 V / rated value
kW 7.5
  • at AC-3 / at 400 V / rated value
kW 7.5
  • at AC-4 / at 400 V / rated value
kW 7.5
Active power loss / per conductor / typical W 0.9
Off-load operating frequency    
  • at AC
1/h 5,000
  • at DC
1/h 1,500
Frequency of operation    
  • at AC-1 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-2 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-3 / according to IEC 60947-6-2 / maximum
1/h 1,000
  • at AC-4 / according to IEC 60947-6-2 / maximum
1/h 300
 
Control circuit:
Design of the surge suppressor   with varistor
Type of voltage / of the controlled supply voltage   AC/DC
Control supply voltage / 1    
  • for DC / rated value
V 230
  • for DC / initial rated value
V 200
  • for DC / final rated value
V 280
  • at 50 Hz / for AC / rated value
V 230
  • at 50 Hz / for AC / initial rated value
V 200
  • at 50 Hz / for AC / final rated value
V 280
  • at 60 Hz / for AC / rated value
V 230
  • at 60 Hz / for AC / initial rated value
V 200
  • at 60 Hz / for AC / final rated value
V 280
Working range factor supply voltage rated value / of the magnet coil    
  • at 50 Hz / for AC
  0.7 1.3
  • at 60 Hz / for AC
  0.7 1.3
  • for DC
  0.7 1.3
Apparent pull-in power / of the solenoid / for AC V·A 16.1
Apparent holding power / of the solenoid / for AC Назад в раздел