CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, DC 24V, COM. CAPABILITY, 3-POLE, SZ S0 SCREW TERMINAL

Артикул: 3RT2026-1BB40-0CC0
Производитель: Siemens


Наименование продукта
CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, DC 24V, COM. CAPABILITY, 3-POLE, SZ S0 SCREW TERMINAL
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
    Версия от 2011-11-20
 
 
General technical data:
Product brand name   SIRIUS
Product designation   3RT2 contactor
Size of the contactor   S0
Protection class IP / on the front   IP20
Degree of pollution   3
Installation altitude / at a height over sea level / maximum m 2000
Ambient temperature    
  • during storage
°C -55 80
  • during operating phase
°C -25 60
  • during transport
°C -55 80
Resistance against shock   12.5g / 5 ms and 7.8g / 10 ms
Impulse voltage resistance / rated value kV 6
Insulation voltage / rated value V 690
Resistive loss    
  • per conductor / typical
W 1.6
  • of the magnet coil / for DC / typical
W 5.9
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
  • according to DIN EN 61346-2
  Q
Mechanical operating cycles as operating time    
  • of the contactor / typical
  10000000
  • of the contactor with added auxiliary switch block / typical
  10000000
  • of the contactor with added electronics-compatible auxiliary switch block / typical
  10000000
 
Main circuit:
Number of poles / for main current circuit   3
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating voltage / at AC-3 / rated value    
  • maximum
V 690
Operating current / at AC-1 / at 400 V    
  • at 40 °C ambient temperature / rated value
A 40
  • at 60 °C ambient temperature / rated value
A 35
Operating current    
  • at AC-2 / at 400 V / rated value
A 25
  • at AC-3 / at 400 V / rated value
A 25
  • at AC-4 / at 400 V / rated value
A 15.5
  • with 1 current path / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 4.5
  • with 2 current paths in series / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
  • with 3 current paths in series / at DC-1
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
  • with 1 current path / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 2.5
  • with 2 current paths in series / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 15
  • with 3 current paths in series / at DC-3 / at DC-5
   
  • at 24 V / rated value
A 35
  • at 110 V / rated value
A 35
Service power    
  • at AC-2 / at 400 V / rated value
W 11000
  • at AC-3
   
  • at 400 V / rated value
W 11000
  • at 500 V / rated value
W 11000
  • at 690 V / rated value
W 11000
  • at AC-4 / at 400 V / rated value
W 7500
Operating reactive power / at AC-6b    
  • at 230 V / rated value
var 0
  • at 400 V / rated value
var 0
  • at 690 V / rated value
var 0
Off-load operating frequency 1/h 1500
Frequency of operation    
  • at AC-1 / according to IEC 60947-6-2 / maximum
1/h 1000
  • at AC-2 / according to IEC 60947-6-2 / maximum
1/h 750
  • at AC-3 / according to IEC 60947-6-2 / maximum
1/h 750
  • at AC-4 / according to IEC 60947-6-2 / maximum
1/h 250
 
Control circuit:
Design of activation of the operating mechanism   conventional
Type of voltage / of the controlled supply voltage   DC
Control supply voltage / 1    
  • for DC
   
  • rated value
V 24
Working range factor supply voltage rated value / of the magnet coil    
  • for DC
  0.8 1.1
Pull-in power / of the solenoid / for DC W 5.9
Holding power / of the solenoid / for DC W 5.9
 
Auxiliary circuit:
Product extension / auxiliary switch   Yes
Contact reliability / of the auxiliary contacts   1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts    
  • instantaneous switching
  1
  • lagging switching
  Назад в раздел