SIMATIC S7-400, CPU 416F-2 CENTRAL PROCESSING UNIT WITH: 1.6 MB WORKING MEMORY (0.8 MB CODE, 0.8 MB DATA), 1. INTERFACE MPI/DP 12 MBIT/S, 2. INTERFACE DP, APPLICABLE W. SOFTWARE PACKAGE DISTRIBUTED SAFETY V5.2

Артикул: 6ES7416-2FK02-0AB0
Производитель: Siemens


Наименование продукта
SIMATIC S7-400, CPU 416F-2 CENTRAL PROCESSING UNIT WITH: 1.6 MB WORKING MEMORY (0.8 MB CODE, 0.8 MB DATA), 1. INTERFACE MPI/DP 12 MBIT/S, 2. INTERFACE DP, APPLICABLE W. SOFTWARE PACKAGE DISTRIBUTED SAFETY V5.2
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2002-12-18 2005-02-15 2005-02-15 2011-10-01
    Версия от 2012-02-18
 
SIMATIC S7-400, CPU 416F-2 CENTRAL PROCESSING UNIT WITH: 1.6 MB WORKING MEMORY (0.8 MB CODE, 0.8 MB DATA), 1. INTERFACE MPI/DP 12 MBIT/S, 2. INTERFACE DP, APPLICABLE W. SOFTWARE PACKAGE DISTRIBUTED SAFETY V5.2
CiR - Configuration in RUN
CiR synchronization time, basic load 100 ms
CiR synchronization time, time per I/O slave 120 µs
Input current
from backplane bus 5 V DC, typ. 1.5 A
from backplane bus 5 V DC, max. 1.6 A
from backplane bus 24 V DC, max. 300 mA; Total current consumption of the components connected to the MPI/DP interfaces, but no more than 150 mA per interface
Power losses
Power loss, typ. 7.5 W
Backup battery
Battery operation
Backup current, typ. 40 µA
Backup current, max. 420 µA
Memory
Work memory
integrated 1.6 Mbyte; 0.8 MB for program; 0.8 MB for data
Load memory
expandable FEPROM with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte
integrated RAM, max. 256 Kibyte
expandable RAM with Memory Card (RAM)
expandable RAM, max. 64 Mbyte
Backup
with battery all data
CPU processing times
for bit operations, min. 0.08 µs
for word operations, min. 0.08 µs
for fixed point arithmetic, min. 0.08 µs
for floating point arithmetic, min. 0.48 µs
CPU-blocks
DB
Number, max. DB 0 reserved
Size, max. 64 Kibyte
FB
Size, max. 64 Kibyte
FC
Size, max. 64 Kibyte
OB
Size, max. 64 Kibyte
Counters, timers and their retentivity
S7 times
Time range
lower limit 10 ms
upper limit 9990 s
Data areas and their retentivity
Flag
Number, max. 16 Kibyte
Retentivity available MB 0 to MB 16383
Number of clock memories 1 memory byte
Data blocks
Number, max. DB 0 reserved
Size, max. 64 Kibyte
Address area
I/O address area
Inputs 16 Kibyte
Outputs 16 Kibyte
of which, distributed
MPI/DP interface, inputs 2 Kibyte
MPI/DP interface, outputs 2 Kibyte
DP interface, inputs 8 Kibyte
DP interface, outputs 8 Kibyte
Process image
Inputs, adjustable 16 Kibyte
Outputs, adjustable 16 Kibyte
Inputs, default 512 byte
Outputs, default 512 byte
consistent data, max. 244 byte
Hardware configuration
Expansion devices, max. (of which 6 ER with K-bus)
Multicomputing Max. 4 CPUs (with UR1 or UR2)
Number of DP masters
via CP CP 443-5 Extended
Mixed mode IM + CP permitted IM 467 cannot be used jointly with CP 443-5 Ext.
Number of operable FMs and CPs (recommended)
FM Limited by number of slots and number of connections
CP, point-to-point limited by number of slots
CP, LAN limited by number of connections
PROFIBUS and Ethernet CPs incl. CP 443-5 Ext. and IM 467
Time of day
Clock
Resolution 1 ms
1st interface
MPI
Services
Transmission rate, max. 12 Mbit/s
DP master
Services
Transmission rate, max. 12 Mbit/s
Address area
Inputs, max. 2 Kibyte
Outputs, max. 2 Kibyte
User data per DP slave
Inputs, max. 244 byte
Outputs, max. 244 byte
per slot, max. 128 byte
DP slave
Services
PG/OP communication with interface active
Routing with interface active
Transmission rate, max. 12 Mbit/s
Transfer memory
Inputs 244 byte
Outputs 244 byte
User data per address area, max. 32 byte
User data per address area, of which consistent, max. 32 byte
2nd interface
DP master
Services
Transmission rate, max. 12 Mbit/s
Address area
Address area, max. 8 Kibyte
Inputs, max. 8 Kibyte
Outputs, max. 8 Kibyte
User data per DP slave
Inputs, max. 128 byte
Outputs, max. 128 byte
DP slave
Services
Routing with interface active
Transmission rate, max. 12 Mbit/s
Transfer memory
Inputs 244 byte
Outputs 244 byte
User data per address area, max. 32 byte
User data per address area, of which consistent, max. 32 byte
Isochronous mode
User data per isochronous slave, max. Назад в раздел