SIMATIC WinAC RTX V4.1

Артикул: 6ES7671-0RC04-0YA0
Производитель: Siemens


Наименование продукта
SIMATIC WinAC RTX V4.1
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2004-07-13 2006-05-30
    Версия от 2012-02-26
 
SIMATIC WINAC RTX V4.1, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON FD, CLASS B, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN 2000/XP AND VCI RTX, REFERENCE-HW: SIMATIC PC
General information
Firmware version 4,1
Memory
Work memory
integrated PC RAM can be used (non-paged memory)
Load memory
integrated RAM, max. PC RAM can be used (non-paged memory)
CPU processing times
for bit operations, min. 0.013 µs; typ.
for fixed point arithmetic, min. 0.025 µs; typ.
for floating point arithmetic, min. 0.025 µs; typ.
Reference platform Pentium IV, 2.4 GHz
CPU-blocks
DB
Number, max. Limited only by available PC work memory
Size, max. 64 kbyte
FB
Number, max. Limited only by available PC work memory
Size, max. 64 kbyte
FC
Number, max. Limited only by available PC work memory
Size, max. 64 kbyte
OB
Size, max. 64 kbyte
Number of time alarm OBs 1
Number of delay alarm OBs 1
Number of time interrupt OBs 5
Number of process alarm OBs 1
Nesting depth
per priority class 24
additional within an error OB 24
Counters, timers and their retentivity
S7 counter
Number 512
Retentivity
adjustable Yes
lower limit 0
upper limit 511
preset 8
Counting range
adjustable Yes
lower limit 0
upper limit 999
IEC counter
present Yes
Type SFB
S7 times
Number 512
Retentivity
lower limit 0
upper limit 511
preset 0
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes
Type SFB
Data areas and their retentivity
Retentivity without UPS and PS Extension Board none
Retentivity with UPS all data
Flag
Number, max. 2 kbyte
of which retentive MB 0 to MB 2048
Retentivity preset MB 0 to MB 15
Number of clock memories 8
Address area
I/O address area
Inputs 16 kbyte
Outputs 16 kbyte
of which, distributed
DP interface, inputs 16 kbyte
DP interface, outputs 16 kbyte
Process image
Inputs, adjustable 8 kbyte
Outputs, adjustable 8 kbyte
Inputs, default 512 byte
Outputs, default 512 byte
Subprocess images
Number of subprocess images, max. 15
Digital channels
Inputs 131072
Outputs 131072
Analog channels
Inputs 8192
Outputs 8192
Hardware configuration
Submodules
Number of submodules, max 4
of which PROFIBUS, max. 4; CP 5613, CP 5613-A2
of which Industrial Ethernet, max. 0
Number of operable FMs and CPs (recommended)
FM FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2
CP, point-to-point CP 340, CP 341 distributed
CP, LAN Over PC CP
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes
Clock synchronization
supported No
2nd interface
Type of interface CP 5613, CP 5613-A2
Max. no. of simultaneously operable CPs 4
Physics RS 485 / PROFIBUS
Isolated Yes
Functionality
MPI No
DP master Yes
DP slave No
DP master
Number of connections, max. 50
Services
PG/OP communication Yes
Routing Yes
Global data communication No
S7 basic communication No
S7 communication Yes
Equidistance mode support Yes
SYNC/FREEZE Yes
Activation/deactivation of DP slaves Yes
Direct data exchange (slave-to-slave communication) Yes
DPV0 Yes
DPV1 Yes
Transmission rate, max. 12 Mbit/s
Number of DP slaves, max. 125
Address area
Inputs, max. 16 kbyte
Outputs, max. 16 kbyte
User data per DP slave
Inputs, max.

Назад в раздел