COMMUNICATION PROCESSOR CP 5614 FO, PCI CARD (32BIT) W. MASTER AND SLAVE CONNECTION TO OPT./ELECTR. PB INCL. DP BASE SW W. NCM PC: DP-RAM INTERF. FOR DP-MASTER W. PG AND FDL PROTOCOL, SINGLE LICENSE F.1 INSTALLATION, 2 LANG. (GER, EN),EXECUT. UNDER MS WIN

Артикул: 6GK1561-4FA00
Производитель: Siemens


Наименование продукта
COMMUNICATION PROCESSOR CP 5614 FO, PCI CARD (32BIT) W. MASTER AND SLAVE CONNECTION TO OPT./ELECTR. PB INCL. DP BASE SW W. NCM PC: DP-RAM INTERF. FOR DP-MASTER W. PG AND FDL PROTOCOL, SINGLE LICENSE F.1 INSTALLATION, 2 LANG. (GER, EN),EXECUT. UNDER MS WIN (32BIT) NT4.0 WS,SERVER; 2000PRO, SERVER; XP PRO
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2000-05-01 2006-06-12 2006-06-12 2016-06-12
    Версия от 2011-12-31
 
COMMUNICATION PROCESSOR CP 5614 FO, PCI CARD (32BIT) W. MASTER AND SLAVE CONNECTION TO OPT./ELECTR. PB INCL. DP BASE SW W. NCM PC: DP-RAM INTERF. FOR DP-MASTER W. PG AND FDL PROTOCOL, SINGLE LICENSE F.1 INSTALLATION, 2 LANG. (GER, EN),EXECUT. UNDER MS WIN (32BIT) NT4.0 WS,SERVER; 2000PRO, SERVER; XP PRO
Transmission rate  
Transmission rate  
  • at interface 1 / in accordance with PROFIBUS
 
  • minimum
9.6 kbit/s
  • maximum
12 Mbit/s
  • at interface 2 / in accordance with PROFIBUS
 
  • minimum
9.6 kbit/s
  • maximum
12 Mbit/s
Interfaces  
Number of optical connections / at interface 1 / in accordance with PROFIBUS 2
Number of electrical connections / at interface 2 / in accordance with PROFIBUS 1
Number of electrical connections / for power supply 1
Supply voltage, current consumption, power loss  
Type of power supply / optional external supply Yes
Supply voltage  
  • 1 / from backplane bus
5 V
  • 2 / [nicht versorgt - aus R?ckwandbus]
12 V
  • external
  • minimum
9 V
  • maximum
12 V
Relative symmetrical tolerance  
  • [nicht versorgt - bei 5 V] / [nicht versorgt - bei DC]
5 %
  • [nicht versorgt - bei 12 V] / [nicht versorgt - bei DC]
5 %
Current consumed  
  • 1 / from backplane bus / with DC / maximum
1.4 A
  • 2 / from backplane bus / with DC / maximum
0.3 A
  • [nicht versorgt - aus externer Versorgungsspannung]
 
  • [nicht versorgt - bei 12 V] / [nicht versorgt - bei DC] / [nicht versorgt - maximal]
0.4 A
Resistive loss 8 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
5 60 °C
  • during storage
-40 +70 °C
  • during transport
-40 +70 °C
Relative humidity / at 25 °C / without condensation / during operating / maximum 80 %
Design, dimensions and weight  
Width 18 mm
Height 107 mm
Depth 168 mm
Net weight 300 g
Product properties, functions, components / general  
Number of plug-in cards in the same design / can be plugged in / per PC station 4
Cable length  
  • with POF cable / maximum
50 m
Performance data  
Performance data / open communication  
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum 80
Performance data / PROFIBUS DP  
Service / [nicht versorgt - als DP-Master]  
  • [nicht versorgt - DPV0]
Yes
  • [nicht versorgt - DPV1]
Yes
  • [nicht versorgt - DPV2]
Yes
Number of DP slaves / on DP master / usable 124
Amount of data  
  • of the address area of the inputs / [nicht versorgt - als DP-Master] / [nicht versorgt - gesamt]
30256 byte
  • of the address area of the outputs / [nicht versorgt - als DP-Master] / [nicht versorgt - gesamt]
30256 byte
  • of the address area of the inputs / [nicht versorgt - je DP-Slave]
244 byte
  • of the address area of the outputs / [nicht versorgt - je DP-Slave]
244 byte
  • [nicht versorgt - des Adressbereiches der Diagnosedaten] / [nicht versorgt - je DP-Slave]
244 byte
Service / [nicht versorgt - als DP-Slave]  
  • [nicht versorgt - DPV0]
Yes
  • [nicht versorgt - DPV1]
Yes
Amount of data  
  • of the address area of the inputs / [nicht versorgt - als DP-Slave] / [nicht versorgt - gesamt]
244 byte
  • of the address area of the outputs / [nicht versorgt - als DP-Slave] / [nicht versorgt - gesamt]
244 byte
Performance data / FMS functions  
Number of possible connections / [nicht versorgt - bei FMS-Verbindung] / [nicht versorgt - maximal] 40
Performance data / S7 communication  
Number of possible connections / [nicht versorgt - f?r S7/PG-Kommunikation] / [nicht versorgt - maximal] 50
Performance data / multi-protocol mode  
Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] 50
Number of configurable connections / per PC station 207
Product functions / Diagnosis  
Product function / Port diagnostics Yes
 