COMMUNICATIONSPROCESSOR CP443-1 FOR CONNECTING SIMATIC S7-400 TO INDUST. ETHERN. VIA ISO, TCP/IP AND UDP, S7-COMM., FETCH/WRITE, SEND/RCV WITH AND W/O RFC1006, MULTICAST, PROFINET IO- CONTROLLER, DHCP, SNMP V2, WEB-, DIAGNOS., INITIALISATION VIA LAN, ACCE

Артикул: 6GK7443-1EX20-0XE0
Производитель: Siemens


Наименование продукта
COMMUNICATIONSPROCESSOR CP443-1 FOR CONNECTING SIMATIC S7-400 TO INDUST. ETHERN. VIA ISO, TCP/IP AND UDP, S7-COMM., FETCH/WRITE, SEND/RCV WITH AND W/O RFC1006, MULTICAST, PROFINET IO- CONTROLLER, DHCP, SNMP V2, WEB-, DIAGNOS., INITIALISATION VIA LAN, ACCESS PROTECTION VIA IP-ACCESS LIST, INTEGRATED REAL-TIME SWITCH ERTEC 400, 2XRJ45 CONNECT. FOR LAN WITH 10/100 MBIT/S
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2007-11-09
    Версия от 2012-03-11
 
COMMUNICATIONSPROCESSOR CP443-1 FOR CONNECTING SIMATIC S7-400 TO INDUST. ETHERN. VIA ISO, TCP/IP AND UDP, S7-COMM., FETCH/WRITE, SEND/RCV WITH AND W/O RFC1006, MULTICAST, PROFINET IO- CONTROLLER, DHCP, SNMP V2, WEB-, DIAGNOS., INITIALISATION VIA LAN, ACCESS PROTECTION VIA IP-ACCESS LIST, INTEGRATED REAL-TIME SWITCH ERTEC 400, 2XRJ45 CONNECT. FOR LAN WITH 10/100 MBIT/S
Transmission rate  
Transfer rate / at the interface 1 10 100 Mbit/s
Interfaces  
Number of electrical connections / at interface 1 / in accordance with Industrial Ethernet 2
Supply voltage, current consumption, power loss  
Type of voltage / of supply voltage DC
Power supply / 1 / from backplane bus 5 V
Relative symmetrical tolerance / [nicht versorgt - bei 5 V] / [nicht versorgt - bei DC] 5 %
Consumed current / from backplane bus / at 5 V / for DC / [nicht versorgt - typisch] 1.4 A
Resistive loss 8.6 W
Permitted ambient conditions  
Ambient temperature  
  • during operating
0 60 °C
  • during storage
-40 +70 °C
  • during transport
-40 +70 °C
Relative humidity  
  • at 25 °C / without condensation / during operating / maximum
95 %
Protection class IP IP20
Design, dimensions and weight  
Width 25 mm
Height 290 mm
Depth 210 mm
Net weight 0.7 kg
Product properties, functions, components / general  
Number of modules  
  • per CPU / maximum
14
Performance data / open communication  
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum 64
Data volume  
  • as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum
8 Kibyte
  • as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum
2 Kibyte
Number of possible connections / for open communication / by means of T blocks / maximum 64
Data volume / as user data per ISO on TCP connection / for open communication / by means of T blocks / maximum 1452 byte
Performance data / S7 communication  
Number of possible connections / [nicht versorgt - f?r S7-Kommunikation]  
  • [nicht versorgt - maximal]
128
  • with PG connections / maximum
2
Performance data / multi-protocol mode  
Number of active connections / [nicht versorgt - bei Multiprotokollbetrieb] 128
Performance data / PROFINET communication / as PN IO-Controller  
Number of PN IO-Devices / on PROFINET IO-Controller / usable / total 128
Number of PN IO IRT-Devices / on PROFINET IO-Controller / usable 32
Number of external PN IO lines / with PROFINET / per rack 4
Amount of data  
  • [nicht versorgt - als Nutzdaten f?r Eingangsvariablen] / [nicht versorgt - als PROFINET IO-Controller] / [nicht versorgt - maximal]
4 Kibyte
  • [nicht versorgt - als Nutzdaten f?r Eingangsvariablen] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
4 Kibyte
  • [nicht versorgt - als Nutzdaten f?r Eingangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
240 byte
  • [nicht versorgt - als Nutzdaten f?r Ausgangsvariablen je PN IO-Device] / [nicht versorgt - bei PROFINET IO-Controller] / [nicht versorgt - maximal]
240 byte
Product functions / management, configuration  
Product function / MIB support Yes
Protocol / is supported  
  • SNMP v1
Yes
  • DCP
Yes
  • LLDP
Yes
Product functions / Diagnosis  
Product function / Web-based diagnostics Yes
Product functions / switch  
Product feature / switch Yes
Product function  
  • switch-managed
No
  • for IRT / PROFINET IO switch
Yes
  • Configuration with STEP 7
Yes
Product functions / Redundancy  
Product function  
  • Ring redundancy
Yes
  • Redundancy manager
Yes
  • MRP redundancy protocol
Yes
Product functions / Security  
Product function  
  • ACL - IP-based
Yes
  • switchoff of non-required services
Yes
  • blocking of communication via physical ports
Yes
  • log file for unauthorized access
No
Product functions / Time  
Product function  
  • SICLOCK support
Yes
  • pass on time synchronization
Yes
Protocol / is supported / NTP Yes
 
letzte ?nderung:
Feb 28, 2012

Назад в раздел