BASIC MODULE FOR AS-I, REVERSING START, SPRING-LOADED CONNECTION, MOUNTED ON CONTACTORS 3RT2 S00/ S0 COMM. CAPABLE CONTACTOR REQUIRED

Артикул: 3RA2712-2BB00
Производитель: Siemens


Наименование продукта
BASIC MODULE FOR AS-I, REVERSING START, SPRING-LOADED CONNECTION, MOUNTED ON CONTACTORS 3RT2 S00/ S0 COMM. CAPABLE CONTACTOR REQUIRED
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
BASIC MODULE FOR AS-I, REVERSING START, SPRING-LOADED CONNECTION, MOUNTED ON CONTACTORS 3RT2 S00/ S0 COMM. CAPABLE CONTACTOR REQUIRED
 
General technical data:
product brand name   Sirius
product designation   AS-i basic module for reversing start spring-loaded terminal
Design of the product   reversing starter function
Size of the contactor / can be combined / company-specific   S00, S0
Protection class IP / on the front   IP20
Degree of pollution   3
Insulation voltage / with degree of pollution 3    
  • rated value
V 690
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during storage
°C -40 +80
  • during operating
°C -25 +60
  • during transport
°C -40 +80
EMC immunity to interference    
  • according to IEC 60947-1
  ambience A (industrial sector)
EMC emitted interference    
  • according to IEC 60947-1
  CISPR11, ambience A (industrial sector)
Conductor-bound parasitic coupling BURST    
  • according to IEC 61000-4-4
  2 kV network connection / 1 kV control connection
Conductor-bound parasitic coupling conductor-earth SURGE    
  • according to IEC 61000-4-5
  1 kV
Conductor-bound parasitic coupling conductor-conductor SURGE    
  • according to IEC 61000-4-5
  0.5 kV
Electrostatic discharge    
  • according to IEC 61000-4-2
  8 kV
Field-bound parasitic coupling    
  • according to IEC 61000-4-3
  10 V/m
Resistance against shock   11g / 15 ms
Resistance against vibration   10 ... 55 Hz / 0.35 mm
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
  • according to DIN EN 61346-2
  K
Acceptability for application    
  • direct starter
  No
  • star-delta starter
  No
  • reversing starter
  Yes
 
Communication:
Product function    
  • bus-communication
  Yes
  • control circuit interface with AS interface
  Yes
 
Control circuit:
Design of the surge suppressor   suppressor diode
Type of voltage / of the controlled supply voltage   DC
Control supply voltage / 1 / for DC / rated value V 24
 
 
Installation/mounting/dimensions:
Built in orientation   any
Type of mounting   can be plugged into contactor
Width mm 45
Height mm 39
Depth mm 75
 
Connections:
Product function    
  • removable terminal for auxiliary and control circuit
  Yes
Design of the electrical connection    
  • for auxiliary and control current circuit
  spring-loaded terminals
Type of the connectable conductor cross-section    
  • for auxiliary contacts
   
  • solid
  1x (0.25 ... 1.5 mm²), 2x (0.25 ... 1.5 mm²)
  • finely stranded
   
  • with conductor end processing
  1x (0.25 ... 1.5 mm²), 2x (0.25 ... 1.5 mm²)
  • without conductor final cutting
  1x (0.25 ... 1.5 mm²), 2x (0.25 ... 1.5 mm²)
  • for AWG conductors / for auxiliary contacts
  2x (24 ... 16)
 
Certificates/approvals:
Verification of suitability   CE / UL / CSA
General Product Approval Test Certificates
 
 
 