AUX.SWITCH BL 11U,2NO+2NC,FRONT CURR.PATH: 1NO, 1NC, 1NC, 1NO, F. CONT. RELAYS A. MOTOR CONT., SZ S00 AND S0, SPRING-LOADED TERMINAL .3 / .4,.1 / .2,.5 /.6,.7 / .8

Артикул: 3RH2911-2FB22
Производитель: Siemens


Наименование продукта
AUX.SWITCH BL 11U,2NO+2NC,FRONT CURR.PATH: 1NO, 1NC, 1NC, 1NO, F. CONT. RELAYS A. MOTOR CONT., SZ S00 AND S0, SPRING-LOADED TERMINAL .3 / .4,.1 / .2,.5 /.6,.7 / .8
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
    Версия от 2011-08-28
 
AUX. SWITCH BLOCK 11U, 2NO+2NC COND. PATHS: 1NO, 1NC, 1NC, 1NO, F. CONT. RELAYS A. MOTOR CONT. SZ S00 AND S0, SPRING-LOADED TERMINAL DIN EN 50005
 
General technical data:
Product brand name   SIRIUS
Product designation   auxiliary switch can be snapped onto the front side
Acceptability for application   Contactor relay and power contactor
Size of the contactor   S00
Protection class IP / on the front   IP20
Ambient temperature    
  • during storage
°C -55 80
  • during operating phase
°C -25 60
Mechanical operating cycles as operating time    
  • typical
  10000000
Electrical operating cycles as operating time / at AC-15 / at 230 V    
  • typical
  200000
Contact reliability   one incorrect switching operation of 100 million switching operations (17 V, 5 mA)
Contact reliability / of the auxiliary contacts   one incorrect switching operation of 100 million switching operations (17 V, 5 mA)
Insulation voltage / with degree of pollution 3    
  • rated value
V 690
Impulse voltage resistance    
  • rated value
kV 6
 
Auxiliary circuit:
Number of NC contacts / for auxiliary contacts    
  • instantaneous switching
  1
  • lagging switching
  1
Number of NO contacts / for auxiliary contacts    
  • instantaneous switching
  1
  • leading switching
  1
Number of changeover contacts / of the auxiliary contacts    
  • instantaneous switching
  0
Operating current / of the auxiliary contacts    
  • at AC-12
   
  • at 24 V
A 6
  • at 230 V
A 6
  • at 400 V
A 6
  • at 690 V
A 6
  • maximum
A 6
  • at AC-14
   
  • at 125 V
A 6
  • at 250 V
A 6
  • at AC-15
   
  • at 24 V
A 6
  • at 230 V
A 6
  • at 690 V
A 1
  • at 400 V
A 3
  • at DC-13
   
  • at 24 V
A 10
  • at 48 V
A 2
  • at 60 V
A 2
  • at 110 V
A 1
  • at 125 V
A 0.9
  • at 220 V
A 0.3
  • at 250 V
A 0.3
 
Installation/mounting/dimensions:
Type of mounting   snap-on mounting
Width mm 36
Height mm 41.5
Depth mm 66
 
Connections:
Design of the electrical connection    
  • for auxiliary and control current circuit
  spring-loaded terminals
Type of the connectable conductor cross-section    
  • for auxiliary contacts
   
  • solid
  2x (0.5 ... 2.5 mm2)
  • finely stranded
   
  • with conductor end processing
  2x (0.5 ... 1.5 mm2)
  • without conductor final cutting
  2 x (0.5 ... 1.5 mm2)
  • for AWG conductors / for auxiliary contacts
  2x (20 ... 14)
 
Certificates/approvals:
Verification of suitability   CE / UL / CSA / CCC
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RH2911-2FB22/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RH2911-2FB22
 
 
 
last change:
Oct 25, 2010

Назад в раздел