CONTACTOR RELAY LATCHED, 3NO+1NC, DC 220V, SIZE S00, SCREW TERMINAL

Артикул: 3RH2431-1BM40
Производитель: Siemens


Наименование продукта
CONTACTOR RELAY LATCHED, 3NO+1NC, DC 220V, SIZE S00, SCREW TERMINAL
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2010-05-01
    Версия от 2011-11-25
 
CONT. RELAY LATCHED, 3S+1OE DC 220V, SIZE S00 SCREW TERMINALS
 
General technical data:
Product brand name   SIRIUS
Product designation   contactor relay
Size of the contactor   S00
Protection class IP / frontal/front side   IP20
Degree of pollution   3
Insulation voltage / with degree of pollution 3 / rated value V 690
Altitude of installation site / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during transport
°C -55 80
  • during storage
°C -55 80
  • during the operating phase
°C -25 60
Impulse voltage resistance / rated value kV 6
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
  • according to DIN EN 61346-2
  K
Mechanical operating cycles as operating time    
  • of the contactor / typical
  10,000,000
  • of the contactor with added auxiliary switch block / typical
  10,000,000
  • of the contactor with added electronics-compatible auxiliary switch block / typical
  10,000,000
 
Control circuit:
Type of voltage / of the controlled supply voltage   DC
Control supply voltage / 1    
  • for DC / rated value
V 220
Operating range factor control supply voltage rated value / of solenoid    
  • for DC
  0.8 1.1
Holding power / of solenoid / with DC W 4
Pull-in power / of the solenoid / with DC W 4
Resistive loss / of the magnet coil / at DC / typical W 4
 
Auxiliary circuit:
Product extension / auxiliary switch   No
Identification number and letter for switching elements   31 E
Contact reliability / of the auxiliary contacts   1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contact   1
  • instantaneous switching
  1
  • delayed switching
  0
  • asynchronous switching
  0
  • lagging switching
  0
Number of NO contacts / for auxiliary contact   3
  • instantaneous switching
  3
  • delayed switching
  0
  • asynchronous switching
  0
  • leading switching
  0
Number of changeover contacts    
  • for auxiliary contact
  0
Operating current / of the auxiliary contacts    
  • at AC-12 / maximum
A 10
  • at AC-15
   
  • at 230 V
A 10
  • at 400 V
A 3
  • at 500 V
A 2
  • at 690 V
A 1
  • with 1 current path
   
  • at DC-12
   
  • at 24 V
A 6
  • at 110 V
A 3
  • at 220 V
A 1
  • at DC-13
   
  • at 24 V
A 6
  • at 110 V
A 1
  • at 220 V
A 0.3
 
Short-circuit:
Design of the fuse link / for short-circuit protection of the auxiliary switch    
  • required
  fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
 
Installation/mounting/dimensions:
built in orientation   vertical
Type of fixing/fixation   screw and snap-on mounting onto 35 mm standard mounting rail
Width mm 90
Height mm 57.5
Depth mm 73
distance, to be maintained, to the ranks assembly    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 0
  • downwards
mm 0
  • sidewards
mm 0
distance, to be maintained, to earthed part    
  • forwards
mm 6
  • backwards
mm 0
  • upwards
mm 6
  • downwards
mm 6
  • sidewards
mm 6
distance, to be maintained, conductive elements    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 0
  • downwards
mm

Назад в раздел