General features | |
Processor | Intel Pentium M Technology (2nd Generation); Intel Celeron M 370, 1.5 GHz, 400 MHz FSB, 1MB SLC; Intel Pentium M 730, 1.6 GHz, 533 MHz FSB, 2MB SLC; Intel Pentium M 760, 2.0 GHz, 533 MHz FSB, 2MB SLC |
Memory type | DDR2-533 |
Main memory | 256 MB to 2 GB |
Free slots | 2x PCI (slots with board retainer), 1x slot for Compact Flash Card |
Operating system | Windows 2000 Prof. (Multi Language), Windows XP Prof. (Multi Language), opt. without operating system |
Additional info on operating system | Multi Language: DE, EN, IT, FR, SP, KOR, CHN (Traditional), CHN (Simplified), JPN |
SIMATIC Software | Optionally in package with SIMATIC WinCC or WinCC flexible |
Drives | |
Diskette drive | optional: via external USB diskette drive |
Optical drives | optional: DVD-ROM or DVD±R±RW combi-drive; on rear, can be operated from side |
Hard disk/Mass storage | 3.5" SATA-RAID hard disk e 40 GB, optional e 80 GB, optional: 2x 2.5" SATA hard disk module(e 60GB). RAID1 controller on board. All drives with vibration-resistant mountings. |
interfaces | |
Graphics interface | DVI-I usable for additional display unit (VGA via adapter); color depth 32 bit,, 8-128 MB Shared Memory |
Connection for keyboard/mouse | USB / USB |
Parallel interface | optional: via PCI card |
serial interface | COM1: 1 x V.24 (RS232) |
PROFIBUS/MPI | onboard, isolated, max. 12 Mbit/s, no plug-in card necessary, CP5611-compatible |
USB | 1x at front, 4x at rear, USB 2.0 (500mA) |
Ethernet | onboard, 2 x 10/100 Mbps, RJ-45, no plug-in card necessary |
Multimedia | no |
Supply voltage | |
Supply voltage | 110 V / 230 V AC (autorange) 50/60 Hz; optional 24 V DC |
Monitoring functions | |
Temperature | Yes |
Watchdog | Yes |
Status LEDs | Power, temperature (on front panel) |
Degree of protection | |
Front to EN 60529 | IP65 (on front) to EN60529 and NEMA4 |
Ambient conditions | |
Vibration load in operation | Tested to DIN IEC 68-2-6: 10 to 58 Hz: 0.075 mm, 58 to 200 Hz: 9.8 m/s2 (1 g) |
Shock loading in operation | Tested to DIN IEC 68-2-29: 50 m/s2 (5g), 30 ms, 100 shocks |
Relative humidity | Tested to DIN IEC 68-2-3, DIN IEC 68-2-30, DIN IEC 68-2-56: 5% to 80% at 25 °C (no condensation) |
Ambient temperature in operation | In full configuration: +5°C to +45°C or +5°C to +50°C in installation space, if at front max. 40°C |
Certifications & Standards | |
Approval | CE, CULus (508) |
EMC | CE, EN 55011, EN 61000-6-4, EN 61000-6-2 |
| |