CONTACTOR, AC-3 3 KW/400 V, 1 NO, AC 24 V, 50/60 HZ, 3-POLE, SIZE S00, SCREW CONNECTION MULTI-UNIT PACKING PACKING = 144 ITEMS 2X4 LAYERS+FILLING MATERIAL

Артикул: 3RT1015-1AB01-ZW95
Производитель: Siemens


Наименование продукта
CONTACTOR, AC-3 3 KW/400 V, 1 NO, AC 24 V, 50/60 HZ, 3-POLE, SIZE S00, SCREW CONNECTION MULTI-UNIT PACKING PACKING = 144 ITEMS 2X4 LAYERS+FILLING MATERIAL
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2006-07-07
CONTACTOR, AC-3 3 KW/400 V, 1 NO, AC 24 V, 50/60 HZ, 3-POLE, SIZE S00, SCREW CONNECTION MULTI-UNIT PACKING PACKING = 144 ITEMS 2X4 LAYERS+FILLING MATERIAL
 
General details:
product brand name   SIRIUS
product designation   power contactor
Size of the contactor   S00
Protection class IP / on the front   IP20
Degree of pollution   3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature / during operating °C -25 +60
Active power loss / per conductor / typical W 0.42
Item designation    
  • according to DIN EN 61346-2
  Q
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
Mechanical operating cycles as operating time    
  • of the contactor / typical
  30,000,000
  • of the contactor with added auxiliary switch block / typical
  10,000,000
  • of the contactor with added electronics-compatible auxiliary switch block / typical
  5,000,000
 
Main circuit:
Number of poles / for main current circuit   3
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating current / at AC-1 / at 400 V / at 40 °C ambient temperature / rated value A 18
Operating current / at AC-1 / at 400 V / at 60 °C ambient temperature / rated value A 16
Operating current    
  • at AC-3 / at 400 V / rated value
A 7
  • with 1 current path
   
  • at DC-1
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 1.5
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 0.1
  • with 2 current paths in series
   
  • at DC-1
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 8.4
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 0.25
  • with 3 current paths in series
   
  • at DC-1
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 15
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 15
  • at 110 V / rated value
A 15
Service power    
  • at AC-1 / at 400 V / rated value
kW 11
  • at AC-2 / at 400 V / rated value
kW 3
  • at AC-3
   
  • at 400 V / rated value
kW 3
  • at 500 V / rated value
kW 3.5
  • at 690 V / rated value
kW 4
 
Control circuit:
Design of activation   conventional
Type of voltage / of the controlled supply voltage   AC
Control supply voltage frequency    
  • 1 / rated value
Hz 50
  • 2 / rated value
Hz 60
Control supply voltage / 1    
  • at 50 Hz / for AC
   
  • rated value
V 24
  • at 60 Hz / for AC
   
  • rated value
V 24
 
Auxiliary circuit:
Contact reliability / of the auxiliary contacts   1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts    
  • instantaneous switching
  0
  • lagging switching
  0
Number of NO contacts / for auxiliary contacts    
  • instantaneous switching
  1
  • leading switching
  0
Operating current / of the auxiliary contacts    
  • at AC-12 / maximum
A 10
  • at AC-15
   
  • at 230 V
A 6
  • at 400 V
A 3
  • at DC-12
   
  • at 60 V
A 6
  • at 110 V
A 3
  • at 220 V
A 1
  • at DC-13
   
  • at 24 V
A 10
  • at 60 V
A 2
  • at 110 V
A 1
  • at 220 V
A 0.3
 
Short-circuit:
Design of the fuse link    
  • for short-circuit protection of th

Назад в раздел