COUPLING RELAY, AC-3 4KW/400 V, 3-POLE, SIZE S00, 1 NO, 24 V DC, 0.85...1.85 X US, 1.4 W, SCREW CONNECTION, DIODE BUILT-IN

Артикул: 3RT1016-1VB41
Производитель: Siemens


Наименование продукта
COUPLING RELAY, AC-3 4KW/400 V, 3-POLE, SIZE S00, 1 NO, 24 V DC, 0.85...1.85 X US, 1.4 W, SCREW CONNECTION, DIODE BUILT-IN
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01
    Версия от 2011-11-27
 
COUPLING RELAY, AC-3 4KW/400 V, 3-POLE, SIZE S00, 1 NO, 24 V DC, 0.85...1.85 X US, 1.4 W, SCREW CONNECTION, DIODE BUILT-IN
 
General details:
Product brand name   SIRIUS
product designation   Coupling relay
Size of the contactor   S00
Protection class IP / on the front   IP20
Degree of pollution   3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature / during operating °C -25 60
Active power loss / per conductor / typical W 0.7
Item designation    
  • according to DIN EN 61346-2
  Q
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  K
Mechanical operating cycles as operating time    
  • of the contactor / typical
  30,000,000
 
Main circuit:
Number of poles / for main current circuit   3
Number of NC contacts / for main contacts   0
Number of NO contacts / for main contacts   3
Operating current / at AC-1 / at 400 V / at 40 °C ambient temperature / rated value A 22
Operating current / at AC-1 / at 400 V / at 60 °C ambient temperature / rated value A 20
Operating current    
  • at AC-3 / at 400 V / rated value
A 9
  • with 1 current path
   
  • at DC-1
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 2.1
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 0.15
  • with 2 current paths in series
   
  • at DC-1
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 12
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 0.35
  • with 3 current paths in series
   
  • at DC-1
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 20
  • at DC-3 / at DC-5
   
  • at 24 V / rated value
A 20
  • at 110 V / rated value
A 20
Service power    
  • at AC-1 / at 400 V / rated value
kW 13
  • at AC-2 / at 400 V / rated value
kW 4
  • at AC-3
   
  • at 400 V / rated value
kW 4
  • at 500 V / rated value
kW 4.5
  • at 690 V / rated value
kW 5.5
 
Control circuit:
Design of activation   conventional
Design of the surge suppressor   with diode
Type of voltage / of the controlled supply voltage   DC
Control supply voltage / 1    
  • for DC
   
  • rated value
V 24
 
Auxiliary circuit:
Contact reliability / of the auxiliary contacts   1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts    
  • instantaneous switching
  0
  • lagging switching
  0
Number of NO contacts / for auxiliary contacts    
  • instantaneous switching
  1
  • leading switching
  0
Operating current / of the auxiliary contacts    
  • at AC-12 / maximum
A 10
  • at AC-15
   
  • at 230 V
A 6
  • at 400 V
A 3
  • at DC-12
   
  • at 60 V
A 6
  • at 110 V
A 3
  • at 220 V
A 1
  • at DC-13
   
  • at 24 V
A 10
  • at 60 V
A 2
  • at 110 V
A 1
  • at 220 V
A 0.3
 
Short-circuit:
Design of the fuse link    
  • for short-circuit protection of the auxiliary switch / required
  fuse gL/gG: 10 A
  • for short-circuit protection of the main circuit
   
  • with type of assignment 1 / required
  fuse gL/gG: 35 A
  • at type of coordination 2 / required
  fuse gL/gG: 20 A
 
Installation/mounting/dimensions:
Type of mounting   screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
series installation   Yes
Width mm 45
Height mm 57.5
Depth mm 72
Distance, to be