OVERLOAD RELAY 30...36 A FOR MOTOR PROTECTION SZ S0, CLASS 10, STAND-ALONE INSTALLATION MAIN CIRCUIT: SCREW TERMINAL AUX. CIRCUIT: SCREW TERMINAL MANUAL-AUTOMATIC-RESET

Артикул: 3RU2126-4PB1
Производитель: Siemens


Наименование продукта
OVERLOAD RELAY 30...36 A FOR MOTOR PROTECTION SZ S0, CLASS 10, STAND-ALONE INSTALLATION MAIN CIRCUIT: SCREW TERMINAL AUX. CIRCUIT: SCREW TERMINAL MANUAL-AUTOMATIC-RESET
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2009-11-19
OVERLOAD RELAY 30...36 A FOR MOTOR PROTECTION SZ S0, CLASS 10, STAND-ALONE INSTALLATION MAIN CIRCUIT: SCREW TERMINAL AUX. CIRCUIT: SCREW TERMINAL MANUAL-AUTOMATIC-RESET
 
General technical data:
product brand name   SIRIUS
product designation   3RU2 thermal overload relay
Protection class IP / on the front   IP20
Insulation voltage / with degree of pollution 3    
  • rated value
V 690
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during transport
°C -55 +80
  • during storage
°C -55 +80
  • during operating
°C -40 +70
Relative humidity    
  • during operating phase
/ % 90
Resistance against shock   8g / 11 ms
Impulse voltage resistance / rated value kV 6
Active power loss / total / typical W 7.5
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  F
  • according to DIN EN 61346-2
  F
Trip class   CLASS 10
Type of assignement   2
Size of overload relay   S0
Size of the contactor / can be combined    
  • company-specific
  S0
 
Main circuit:
Number of poles / for main current circuit   3
Operating voltage / at AC-3 / rated value    
  • maximum
V 690
Operating current / at AC-3 / at 400 V    
  • rated value
A 36
Service power / at AC-3    
  • at 400 V / rated value
kW 18.5
  • at 500 V / rated value
kW 22
  • at 690 V / rated value
kW 30
Adjustable response current    
  • of the current-dependent overload release
A 30 36
Operating current / of the fuse link / rated value A 80
 
Auxiliary circuit:
Contact reliability / of the auxiliary contacts   < 1 error per 100 million operating cycles
Number of NC contacts / for auxiliary contacts   1
Number of NO contacts / for auxiliary contacts   1
Number of change-over switches / for auxiliary contacts   0
Operating current / of the auxiliary contacts    
  • at AC-15
   
  • at 24 V
A 3
  • at 110 V
A 3
  • at 120 V
A 3
  • at 125 V
A 3
  • at 230 V
A 2
  • at 400 V
A 1
  • at DC-13
   
  • at 24 V
A 1
  • at 110 V
A 0.22
  • at 125 V
A 0.22
  • at 220 V
A 0.11
 
Short-circuit:
Design of the fuse link / for short-circuit protection of the auxiliary switch / required   fuse gG: 10 A
 
Installation/mounting/dimensions:
Built in orientation   vertical
Type of mounting   stand-alone installation
Width mm 45
Height mm 87
Depth mm 73
Distance, to be maintained, to the ranks assembly    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 6
  • downwards
mm 6
  • sidewards
mm 6
Distance, to be maintained, to earthed part    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 6
  • downwards
mm 6
  • sidewards
mm 6
Distance, to be maintained, conductive elements    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 6
  • downwards
mm 6
  • sidewards
mm 6
 
Connections:
Design of the electrical connection    
  • for main current circuit
  screw-type terminals
  • for auxiliary and control current circuit
  screw-type terminals
Product function / removable terminal for auxiliary and control circuit   No
Type of the connectable conductor cross-section    
  • for main contacts
   
  • solid
 <

Назад в раздел