| CIRCUIT-BREAKER SZ S00, FOR MOTOR PROTECTION, CLASS 10, A-RELEASE 9..12.5A, N-RELEASE 163A, SCREW CONNECTION, STANDARD SW. CAPACITY |
|
General technical data: |
product brand name | | SIRIUS |
product designation | | 3RV2 circuit breaker |
Size of the circuit-breaker | | S00 |
Trip class | | CLASS 10 |
Protection class IP / on the front | | IP20 |
Degree of pollution | | 3 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Ambient temperature | | |
| °C | -50… +80 |
| °C | -20… +60 |
| °C | -50… +80 |
Resistance against shock | | 25g / 11 ms |
Impulse voltage resistance / rated value | kV | 6 |
Insulation voltage / rated value | V | 690 |
Active power loss / total / typical | W | 7.3 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | F |
- according to DIN EN 61346-2
| | F |
Mechanical operating cycles as operating time | | |
- of the main contacts / typical
| | 100,000 |
- of the auxiliary contacts / typical
| | 100,000 |
Type of the driving mechanism / motor drive | | No |
Design of the operating mechanism | | selector switch |
Product function | | |
| | Yes |
- phase disturbance recognition
| | Yes |
Product component | | |
| | No |
- undervoltage release mechanism
| | No |
| | No |
Product extension / optional / motor drive | | No |
|
Main circuit: |
Number of poles / for main current circuit | | 3 |
Operating voltage / at AC-3 / rated value / maximum | V | 690 |
Operating current / at AC-3 / at 400 V / rated value | A | 11.5 |
Service power / at AC-3 | | |
| W | 5,500 |
| W | 7,500 |
| W | 7,500 |
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum | 1/h | 15 |
Arrangement of electrical connectors / for main current circuit | | Top and bottom |
Adjustable response current | | |
- of the non-delayed short-circuit release
| A | 163… 163 |
- of the current-dependent overload release
| A | 9… 12.5 |
Service power / at AC-3 / at 230 V / rated value | W | 3,000 |
Continuous current / rated value | A | 12.5 |
|
Auxiliary circuit: |
Product extension / auxiliary switch | | Yes |
Number of NC contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of NO contacts / for auxiliary contacts / instantaneous switching | | 0 |
Number of change-over switches / for auxiliary contacts | | 0 |
|
Inputs/ Outputs: |
Number of digital inputs | | 0 |
|
Short-circuit: |
Breaking capacity limit short-circuit current (lcu) | | |
| A | 100,000 |
| A | 42,000 |
| A | 6,000 |
Design of the overcurrent release and short-circuit release | | thermomagnetic |
|
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
Width | mm | 45 |
Height | mm | 97 |
Depth | mm | 91 |
Distance, to be maintained, to the ranks assembly | | |
| mm | 0 |
| mm | 0 |
| mm | 50 |
| mm | 50 |
| mm | 0 |
Distance, to be maintained, to earthed part | | |
| mm | 0 |
| mm | 0 |
| mm | 50 |
| mm | 30 |
| mm | 50 |
Distance, to be maintained, conductive elements | | |
| mm | 0 |
| mm | 0 |
| mm | 50 |
| mm | 50 |
| mm | 30 |
|
Connections: |
Product function | | |
|