CIRCUIT-BREAKER SZ S00, FOR TRANSFORMER PROT. A-RELEASE 1.8...2.5A, N-RELEASE 52A SCREW CONNECTION, STANDARD SW. CAPACITY

Артикул: 3RV2411-1CA10
Производитель: Siemens


Наименование продукта
CIRCUIT-BREAKER SZ S00, FOR TRANSFORMER PROT. A-RELEASE 1.8...2.5A, N-RELEASE 52A SCREW CONNECTION, STANDARD SW. CAPACITY
Жизненный цикл продукта
3RV2411-1CA10">
3RV2411-1CA10"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
3RV2411-1CA10"> 2009-11-19
CIRCUIT-BREAKER SZ S00, FOR TRANSFORMER PROT. A-RELEASE 1.8...2.5A, N-RELEASE 52A SCREW CONNECTION, STANDARD SW. CAPACITY
 
General technical data:
product brand name   SIRIUS
product designation   3RV2 circuit breaker
Size of the circuit-breaker   S00
Trip class   CLASS 10
Protection class IP / on the front   IP20
Degree of pollution   3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature    
  • during storage
°C -50 +80
  • during operating
°C -20 +60
  • during transport
°C -50 +80
Resistance against shock   25g / 11 ms
Impulse voltage resistance / rated value kV 6
Insulation voltage / rated value V 690
Active power loss / total / typical W 6
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  F
  • according to DIN EN 61346-2
  F
Mechanical operating cycles as operating time    
  • of the main contacts / typical
  100,000
  • of the auxiliary contacts / typical
  100,000
Type of the driving mechanism / motor drive   No
Design of the operating mechanism   selector switch
Product function    
  • overload protection
  Yes
  • phase disturbance recognition
  Yes
Product component    
  • auxiliary switch
  No
  • undervoltage release mechanism
  No
  • trip indicator
  No
Product extension / optional / motor drive   No
 
Main circuit:
Number of poles / for main current circuit   3
Operating voltage / at AC-3 / rated value / maximum V 690
Operating current / at AC-3 / at 400 V / rated value A 1.9
Service power / at AC-3    
  • at 400 V / rated value
W 750
  • at 500 V / rated value
W 1,100
  • at 690 V / rated value
W 1,500
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum 1/h 15
Arrangement of electrical connectors / for main current circuit   Top and bottom
Adjustable response current    
  • of the non-delayed short-circuit release
A 52 52
  • of the current-dependent overload release
A 1.8 2.5
Service power / at AC-3 / at 230 V / rated value W 370
Continuous current / rated value A 2.5
 
Auxiliary circuit:
Product extension / auxiliary switch   Yes
Number of NC contacts / for auxiliary contacts / instantaneous switching   0
Number of NO contacts / for auxiliary contacts / instantaneous switching   0
Number of change-over switches / for auxiliary contacts   0
 
Inputs/ Outputs:
Number of digital inputs   0
 
Short-circuit:
Breaking capacity limit short-circuit current (lcu)    
  • at 400 V / rated value
A 100,000
  • at 500 V / rated value
A 100,000
  • at 690 V / rated value
A 10,000
Design of the overcurrent release and short-circuit release   thermomagnetic
 
Installation/mounting/dimensions:
Built in orientation   any
Type of mounting   screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Width mm 45
Height mm 97
Depth mm 91
Distance, to be maintained, to the ranks assembly    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 50
  • downwards
mm 50
  • sidewards
mm 0
Distance, to be maintained, to earthed part    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 50
  • sidewards
mm 30
  • downwards
mm 50
Distance, to be maintained, conductive elements    
  • forwards
mm 0
  • backwards
mm 0
  • upwards
mm 50
  • downwards
mm 50
  • sidewards
mm 30
 
Connections:
Product function    
  • removable terminal for main circuit
<