DIGITAL MONITORING RELAY COS-PHI AND CURRENT MONITORING FOR IO-LINK 90 TO 690V AC, 0.2 TO 10A OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 3.0A 2 CHANGE-OVER CONTACTS, SCREW TERMINAL

Артикул: 3UG4841-1CA40
Производитель: Siemens


Наименование продукта
DIGITAL MONITORING RELAY COS-PHI AND CURRENT MONITORING FOR IO-LINK 90 TO 690V AC, 0.2 TO 10A OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 3.0A 2 CHANGE-OVER CONTACTS, SCREW TERMINAL
Жизненный цикл продукта
3UG4841-1CA40">
3UG4841-1CA40"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
3UG4841-1CA40"> 2011-10-31
DIGITAL MONITORING RELAY COS-PHI AND CURRENT MONITORING FOR IO-LINK 90 TO 690V AC, 0.2 TO 10A OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 3.0A 2 CHANGE-OVER CONTACTS, SCREW TERMINAL
Product function   Active power monitoring relay
 
Measuring circuit:
   
Number of poles / for main current circuit   1
Phase number   1
Adaptable response value phase angle ° 0.1 0.99
Type of current / for monitoring   AC
Measurable current A 0.2 10
Adjustable response current    
  • 1
A 0.2 10
  • 2
A 0.2 10
Adjustable response delay time    
  • when starting
s 0 999.9
  • with lower or upper limit violation
s 0 999.9
Adjustable switching hysteresis for measured current value mA 0 3,000
Operating voltage    
  • rated value
V 90 690
Relative metering precision % 10
Precision of digital display   +/-1 digit
Relative repeat accuracy % 1
 
General technical details:
Design of the display   LCD
Product function    
  • overcurrent recognition of 1 phase
  Yes
  • undercurrent recognition of 1 phase
  Yes
  • reset external
  Yes
  • open-circuit or closed-circuit current principle
  Yes
Starting time / after the control supply voltage has been applied ms 1,000
Type of voltage / of the controlled supply voltage   DC
Control supply voltage    
  • at 50 Hz / at AC
   
  • rated value
V 0 0
  • at 60 Hz / at AC
   
  • rated value
V 0 0
  • for DC
   
  • rated value
V 24 24
Working range factor supply voltage rated value    
  • for DC
  0.75 1.25
Impulse voltage resistance / rated value kV 6
Recorded real power W 2
Protection class IP   IP20
Electromagnetic compatibility   IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Resistance against vibration / according to IEC 60068-2-6   1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g
Resistance against shock / according to IEC 60068-2-27   sinusoidal half-wave 15g / 11 ms
Installation altitude / at a height over sea level / maximum m 2,000
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4   2 kV
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5   2 kV
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5   1 kV
Electrostatic discharge / according to IEC 61000-4-2   6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-3   10 V/m
Degree of pollution   2
Ambient temperature    
  • during operating
°C -25 +60
  • during storage
°C -40 +85
  • during transport
°C -40 +85
Galvanic isolation    
  • between entrance and outlet
  Yes
  • between the outputs
  Yes
  • between the voltage supply and other circuits
  Yes
Mechanical operating cycles as operating time / typical   10,000,001
Electrical operating cycles as operating time / at AC-15 / at 230 V / typical   100,000
Operating cycles / with 3RT2 contactor / maximum 1/h 5,000
 
Communication:
   
Type of voltage supply / via input/ output link master   Yes
IO-Link transfer rate   COM2 (38,4 kBaud)
Protocol / will be supported / IO-Link protocol   Yes
Data volume    
  • of the address range of the outputs / with cyclical transfer
byte 2
  • of the address range of the inputs / with cyclical transfer
byte 4
Point-to-point cycle time / between master and IO-Link device / minimum ms 10
 
Mechanical design:
Width mm 22.5
Height mm 102
Depth mm 91
Built in orientation   any
Distance, to be maintained, to earthed part    
  • forwards
mm 0
  • backwards
mm 0
  • sidewards
mm 0
  • upwards
mm 0
  • downwards
mm 0
Distance, to be maintained, to the ranks assembly    
  • forwards