DIGITAL MONITORING RELAY SPEED MONITORING, FOR IO-LINK FROM 0.1 TO 2200 RPM OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 99 RPM 1 CHANGE-OVER CONTACT, SCREW TERMINAL

Артикул: 3UG4851-1AA40
Производитель: Siemens


Наименование продукта
DIGITAL MONITORING RELAY SPEED MONITORING, FOR IO-LINK FROM 0.1 TO 2200 RPM OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 99 RPM 1 CHANGE-OVER CONTACT, SCREW TERMINAL
Жизненный цикл продукта
3UG4851-1AA40">
3UG4851-1AA40"> Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
3UG4851-1AA40"> 2011-10-31
DIGITAL MONITORING RELAY SPEED MONITORING, FOR IO-LINK FROM 0.1 TO 2200 RPM OVERSHOOT AND UNDERSHOOT ON DELAY TIME TRIPPING DELAY TIME HYSTERESIS 0.1 TO 99 RPM 1 CHANGE-OVER CONTACT, SCREW TERMINAL
Product function   RPM monitoring relay
 
Measuring circuit:
   
Adjustable response delay time    
  • when starting
s 0 999.9
  • with lower or upper limit violation
s 0 999.9
Adjustable response value revolution 1/min 0 2,200
Input voltage / at the digital input 1    
  • initial value for signal<0>-recognition
V 0
  • final value for signal<0>-recognition
V 1
  • initial value for signal<1>-recognition
V 4.5
  • final value for signal<1>-recognition
V 30
Input current / at the digital input 2    
  • initial value for signal<0>-recognition
mA 0
  • final value for signal<0>-recognition
mA 1.2
  • initial value for signal<1>-recognition
mA 2.1
  • final value for signal<1>-recognition
mA 8.2
Design of the input / reducing-entrance   No
Design of the sensor    
  • at the digital input 1 / connectable
  PNP switching three-wire sensor or mechanical impulse contact with external DC supply (4.5 V … 30 V)
  • at the digital input 2 / connectable
  2-conductor Namur sensor or mechanical impulse contact
Input current / at the digital input 1 / maximum mA 50
Pulse duration ms 5
Pulse interval ms 5
Number of sensor signals per revolution   1 10
Switching hysteresis for rotational speed 1/min 0 99.9
 
General technical details:
Design of the display   LCD
Product function    
  • rotation speed monitoring
  Yes
  • standstill monitoring
  No
  • defect storage
  Yes
  • reset external
  Yes
  • self-reset
  Yes
  • manual RESET
  Yes
  • open-circuit or closed-circuit current principle
  Yes
Starting time / after the control supply voltage has been applied ms 500
Response time / maximum ms 100
Relative metering precision % 10
Precision of digital display   +/- 1 Digit
Relative repeat accuracy % 1
Type of voltage / of the controlled supply voltage   DC
Control supply voltage    
  • for DC
   
  • rated value
V 24 24
Working range factor supply voltage rated value    
  • for DC
  0.75 1.25
Impulse voltage resistance / rated value kV 4
Recorded real power W 2
Protection class IP   IP20
Electromagnetic compatibility   IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Resistance against vibration / according to IEC 60068-2-6   1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g
Resistance against shock / according to IEC 60068-2-27   sinusoidal half-wave 15g / 11 ms
Installation altitude / at a height over sea level / maximum m 2,000
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4   2 kV
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5   2 kV
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5   1 kV
Electrostatic discharge / according to IEC 61000-4-2   6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-3   10 V/m
Degree of pollution   2
Apparent power consumed    
  • at 24 V / for DC / maximum
V·A 4
Ambient temperature    
  • during operating
°C -25 +60
  • during storage
°C -40 +80
  • during transport
°C -40 +80
Galvanic isolation    
  • between entrance and outlet
  Yes
  • between the outputs
  No
  • between the voltage supply and other circuits
  Yes
Acceptability for application / safety-related circuits   No
Category / according to EN 954-1   none
safety Integrated Level / according to IEC 61508   none
 
Communication:
   
Type of voltage supply / via input/ output link master   Yes
IO-Link transfer rate   COM2 (38,4 kBaud)
Protocol / will be supported / IO-Link protocol   Yes
Data volume    
  • of the address range of the outputs / with cyclical transfer
byte 2
  • of the address range of the inputs / with cyclical transfer
byte 4
Point-to-point cycle time / between master and IO-Link device / minimum ms 10
 

Назад в раздел