ANALOG MONITORING RELAY PHASE SEQUENCE MONITORING 3X 160 TO 260V AC 50 TO 60 HZ 1 CHANGEOVER CONTACT SCREW TERMINAL REPLACEMENT PRODUCT FOR 3UG3511-1AQ50 OR 3UG3511-1AV50

Артикул: 3UG4511-1AN20
Производитель: Siemens


Наименование продукта
ANALOG MONITORING RELAY PHASE SEQUENCE MONITORING 3X 160 TO 260V AC 50 TO 60 HZ 1 CHANGEOVER CONTACT SCREW TERMINAL REPLACEMENT PRODUCT FOR 3UG3511-1AQ50 OR 3UG3511-1AV50
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2005-05-01
ANALOG MONITORING RELAY PHASE SEQUENCE MONITORING 3X 160 TO 260V AC 50 TO 60 HZ 1 CHANGEOVER CONTACT SCREW TERMINAL REPLACEMENT PRODUCT FOR 3UG3511-1AQ50 OR 3UG3511-1AV50
Product function   Phase monitoring relay
 
Measuring circuit:
   
Type of voltage / for monitoring   AC
Number of poles / for main current circuit   3
Measurable voltage    
  • for AC
V 160 260
 
General technical details:
Type of display / LED   Yes
Product function    
  • undervoltage recognition
  No
  • overvoltage recognition
  No
  • phase sequence recognition
  Yes
  • phase disturbance recognition
  No
  • asymmetry recognition
  No
  • overvoltage recognition of 3 phases
  No
  • undervoltage recognition of 3 phases
  No
  • tension window recognition of 3 phases
  No
  • self-reset
  Yes
  • open-circuit or closed-circuit current principle
  No
Starting time / after the control supply voltage has been applied ms 200
Response time / maximum ms 450
Type of voltage / of the controlled supply voltage   AC
Control supply voltage    
  • at 50 Hz / at AC
   
  • rated value
V 160 260
  • at 60 Hz / at AC
   
  • rated value
V 160 260
Working range factor supply voltage rated value    
  • at 50 Hz
   
  • for AC
  1 1
  • at 60 Hz
   
  • for AC
  1 1
Impulse voltage resistance / rated value kV 6
Recorded real power W 2
Protection class IP   IP20
Electromagnetic compatibility   IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Resistance against vibration / according to IEC 60068-2-6   1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g
Resistance against shock / according to IEC 60068-2-27   sinusoidal half-wave 15g / 11 ms
Installation altitude / at a height over sea level / maximum m 2,000
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4   2 kV
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5   2 kV
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5   1 kV
Electrostatic discharge / according to IEC 61000-4-2   6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / according to IEC 61000-4-3   10 V/m
Insulation voltage / for overvoltage category III according to IEC 60664 / with degree of pollution 3 / rated value V 690
Degree of pollution   3
Ambient temperature    
  • during operating
°C -25 +60
  • during storage
°C -40 +85
  • during transport
°C -40 +85
Galvanic isolation    
  • between entrance and outlet
  Yes
  • between the outputs
  Yes
  • between the voltage supply and other circuits
  Yes
 
 
Mechanical design:
Width mm 22.5
Height mm 83
Depth mm 91
Built in orientation   any
Distance, to be maintained, to earthed part    
  • forwards
mm 0
  • backwards
mm 0
  • sidewards
mm 0
  • upwards
mm 0
  • downwards
mm 0
Distance, to be maintained, to the ranks assembly    
  • forwards
mm 0
  • backwards
mm 0
  • sidewards
mm 0
  • upwards
mm 0
  • downwards
mm 0
Distance, to be maintained, conductive elements    
  • forwards
mm 0
  • backwards
mm 0
  • sidewards
mm 0
  • upwards
mm 0
  • downwards
mm 0
Type of mounting   snap-on mounting
Product function / removable terminal for auxiliary and control circuit   Yes
Design of the electrical connection   screw-type terminals
Type of the connectable conductor cross-section    
  • solid
  1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2)
  • finely stranded
   
  • with wire end processing
  Назад в раздел