| DIGITAL MONITORING RELAY CURRENT MONITORING, 22.5MM FROM 0.1 TO 60V AC/DC OVERSHOOT AND UNDERSHOOT SUPPLY VOLTAGE: AC/DC 24V DC AND AC 50 TO 60 HZ NO GALVANIC ISOLATION FROM MEASURING CIRCUIT INTERF. PEAK DELAY 0.1 TO 20S HYSTERESIS 0.1 TO 30V 1 CO CONTACT W. OR W/O ERROR LOG SPRING-LOADED CONNECTION |
Product function | | Voltage monitoring relay |
|
Measuring circuit: | | |
Type of voltage / for monitoring | | AC/DC |
Number of poles / for main current circuit | | 1 |
Measurable line frequency | Hz | 500… 40 |
Measurable voltage | | |
| V | 0.1… 60 |
Adjustable voltage range | V | 0.1… 60 |
Adjustable response delay time | | |
- with lower or upper limit violation
| s | 0.1… 20 |
Response time / maximum | ms | 450 |
Relative metering precision | % | 5 |
Precision of digital display | | +/-1 digit |
Relative temperature-related measurement deviation | % | 0.1 |
Relative repeat accuracy | % | 1 |
|
General technical details: |
Design of the display | | LCD |
Product function | | |
- tension window recognition of 1 phase
| | Yes |
- tension window recognition of 3 phases
| | No |
- tension window recognition DC
| | Yes |
- overvoltage recognition of 1 phase
| | Yes |
- overvoltage recognition of 3 phases
| | No |
- overvoltage recognition DC
| | Yes |
- undervoltage recognition of 1 phase
| | Yes |
- undervoltage recognition of 3 phases
| | No |
- undervoltage recognition DC
| | Yes |
| | Yes |
| | Yes |
- open-circuit or closed-circuit current principle
| | Yes |
Starting time / after the control supply voltage has been applied | ms | 1,000 |
Type of voltage / of the controlled supply voltage | | AC/DC |
Control supply voltage | | |
| | |
| V | 24… 24 |
| | |
| V | 24… 24 |
| | |
| V | 24… 24 |
Working range factor supply voltage rated value | | |
| | |
| | 0.85… 1.15 |
| | |
| | 0.85… 1.15 |
| | 0.85… 1.15 |
Impulse voltage resistance / rated value | kV | 4 |
Recorded real power | W | 2 |
Protection class IP | | IP20 |
Electromagnetic compatibility | | IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4 |
Resistance against vibration / according to IEC 60068-2-6 | | 1
6 Hz: 15 mm, 6
500 Hz: 2g |
Resistance against shock / according to IEC 60068-2-27 | | sinusoidal half-wave 15g / 11 ms |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Maximum permissible voltage for safe disconnection | | |
- between control and auxiliary circuit
| V | 300 |
- between auxiliary circuit and auxiliary circuit
| V | 300 |
Conductor-bound parasitic coupling BURST / according to IEC 61000-4-4 | | 2 kV |
Conductor-bound parasitic coupling conductor-earth SURGE / according to IEC 61000-4-5 | | 2 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE / according to IEC 61000-4-5 | | 1 kV |
Electrostatic discharge / according to IEC 61000-4-2 | | 6 kV contact discharge / 8 kV air discharge |
Field-bound parasitic coupling / according to IEC 61000-4-3 | | 10 V/m |
Insulation voltage / for overvoltage category III according to IEC 60664 / with degree of pollution 3 / rated value | V | 690 |
Ambient temperature | | |
| °C | -25… +60 |
| °C | -40… +85 |
| °C | -40… +85 |
Design of the electrical isolation | | Safe isolation |
Galvanic isolation | | |
- between entrance and outlet
| | Yes |
| | Yes |
- between the voltage supply and other circuits
| | No |
Mechanical operating cycles as operating time / typical | | 10,000,000 |
Electrical operating cycles as operating time / at AC-15 / at 230 V / typical | | 100,000 |
Operating cycles / with 3RT2 contactor / maximum | 1/h | 5,000 |
|
|
Mechanical design: |
Width | mm | 22.5 |
Height | mm | 94 |
Depth | mm | 91 |
Built in orientation | | any |
Distance, to be maintained, to earthed part | | |
| mm | 0 |
| mm | Назад в раздел
|