CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):3 /15; UPRI(V):420-400-380-360; USEC(V):230-220(2X115-110); ISEC(A):13,0-13,6-26,1-27,3; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLA

Артикул: 4AM9996-3FA00-0CA0
Производитель: Siemens


Наименование продукта
CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):3 /15; UPRI(V):420-400-380-360; USEC(V):230-220(2X115-110); ISEC(A):13,0-13,6-26,1-27,3; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-2>UL/CSA-RECOGNIZED< >CONTROL CIRCUIT TRANSFORMER<
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01 2010-10-01 2010-10-01 2011-10-01
    Версия от 2011-12-07
 
CONTROL CIRCUIT TRANSFORMER; PHASES:1; PN/PN(S6)(KVA):3 /15; UPRI(V):420-400-380-360; USEC(V):230-220(2X115-110); ISEC(A):13,0-13,6-26,1-27,3; F(HZ):50...60; VECTOR GR./SHIELD WNG.:II0 /0; TA/ISOKL:40 /B; IP00; TYPE OF TERMINALS:SCREW CONNECTION; INSTALLATION:SCREW; EN 61558-2-2 >UL/CSA-RECOGNIZED< >CONTROL CIRCUIT TRANSFORMER<
 
General technical details:
product designation   control circuit transformer
Product brand name   SIDAC
Operating apparent output / rated value V·A 3,000
Efficiency   0.95
Manner of switching for transformers   Ii0
Verification of suitability   CE / cRUus
Product function    
  • temperature surveillance
  No
  • isolation control
  No
  • short circuit and overload protection
  No
Number of the protective coils   0
Short-term vector power V·A 15,000
Relative short-circuit voltage % 2.91
 
Inputs:
Phase number / of the inputs   1
Input voltage    
  • _1 / rated value
V 420
  • _2 / rated value
V 400
  • _3 / rated value
V 380
  • _4 / rated value
V 360
Electrical input frequency    
  • minimum
Hz 50
  • maximum
Hz 60
 
Outputs:
Phase number / of the outputs   1
Electrical output frequency    
  • maximum
Hz 60
  • minimum
Hz 50
 
Ambient conditions:
Thermal class / according to IEC 60085   B
Ambient temperature / rated value °C 40
Protection class IP   IP00
 
Mechanical design:
Design of the electrical connection    
  • secondary side / for main current circuit
  screw-type terminals
  • at the input / for main current circuit
  screw-type terminals
Type of mounting   screws
Construction form of the iron core   UI 150/75
 
Certificates/approvals:
   
General Product Approval Shipping Approval other
ROSTEST
PRS (Polski Rejestr Statkow)
Manufacturer other    
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
CAx-Online-Generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/4AM9996-3FA00-0CA0/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=4AM9996-3FA00-0CA0
 
 
 
last change:
Aug 25, 2011