CONTACTOR COMBINATION FOR SAFETY CIRCUITS ENABLING AND SIGNALLING CIRCUIT 5N0+1NC, AC-OPERATION AC OPERATION AC 110V 50/60HZ

Артикул: 3TK2806-0AG2
Производитель: Siemens


Наименование продукта
CONTACTOR COMBINATION FOR SAFETY CIRCUITS ENABLING AND SIGNALLING CIRCUIT 5N0+1NC, AC-OPERATION AC OPERATION AC 110V 50/60HZ
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01
    Версия от 2011-08-27
 
(kein FDB-Text gefunden)
General technical details:
 
Product designation contactor safety assembly
Design of the product for safety circuits
Type of voltage  
  • of the operating voltage
AC/DC
  • of the controlled supply voltage
AC
Operating voltage  
  • 1 / for AC / rated value
230 V
  • 1 / for DC / rated value
24 V
  • 2 / for AC / rated value
400 V
Control supply voltage  
  • at 50 Hz / for AC / rated value / minimum
110 V
  • at 50 Hz / for AC / rated value / maximum
110 V
  • at 60 Hz / for AC / rated value / minimum
110 V
  • at 60 Hz / for AC / rated value / maximum
110 V
Number of outputs  
  • as contact-less semiconductor switching element
 
  • fail-safe / non-delayed
0
  • fail-safe / delayed switching
0
  • for reporting function / non-delayed
0
  • for reporting function / delayed switching
0
  • as contact-affected switching element
 
  • fail-safe / non-delayed
5
  • fail-safe / delayed switching
0
  • for reporting function / non-delayed
1
  • for reporting function / delayed switching
0
Breaking capacity current  
  • at AC-15 / at 24 V
4 A
  • at AC-15 / at 230 V
4 A
  • at AC-15 / at 400 V
3 A
  • at DC-13 / at 24 V
6 A
  • at DC-13 / at 230 V
0.5 A
Product feature / transverse contact-secure Yes
   
Mechanical design:
 
Type of the safety-related wiring / of the inputs single-channel or single-channel and two-channel
Design of the electrical connection screw-type terminals
  • Jumper socket
No
Design of the cascading none
Width 75 mm
Height 97 mm
Depth 148 mm
   
Product Function:
 
Protective door monitoring
Yes
monitored start-up
Yes
Automatic start
No
Step mat monitoring
No
Emergency-OFF function
Yes
Pressing control
No
Light grid monitoring
No
Light barrier monitoring
No
Laser scanner monitoring
No
Magnetic switch monitoring Normally closed contact-Normally closed contact
No
Magnetic switch monitoring Normally closed contact-Normally open contact
No
   
Approbationen/ Zertifikate:
 
Safety Integrated Level / acc. to IEC 61508 none
Security category / acc. to EN 954-1 2
 
letzte ?nderung:
08/24/2006


Назад в раздел