SIRIUS SAFETY RELAY FOR SAFETY-ORIENTED STANDSTILL MONITORING, 230V AC, 45.0MM, SPRING-LOADED TERMINAL, FK INSTANT.: 3NO 1NC, FK DELAYED: 0, MK: 3, AUTO START, BASIC UNIT, MAX. ACHIEV. CAT. EN954-1: 4, MAX. ACHIEV. SIL TO IEC61508:3,

Артикул: 3TK2810-0GA02
Производитель: Siemens


Наименование продукта
SIRIUS SAFETY RELAY FOR SAFETY-ORIENTED STANDSTILL MONITORING, 230V AC, 45.0MM, SPRING-LOADED TERMINAL, FK INSTANT.: 3NO 1NC, FK DELAYED: 0, MK: 3, AUTO START, BASIC UNIT, MAX. ACHIEV. CAT. EN954-1: 4, MAX. ACHIEV. SIL TO IEC61508:3,
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2007-06-01
    Версия от 2012-02-25
 
SIRIUS SAFETY RELAY FOR SAFETY-ORIENTED STANDSTILL MONITORING, 230V AC, 45.0MM, SPRING-LOADED TERMINAL, FK INSTANT.: 3NO 1NC, FK DELAYED: 0, MK: 3, AUTO START, BASIC UNIT, MAX. ACHIEV. CAT. EN954-1: 4, MAX. ACHIEV. SIL TO IEC61508:3,
 
General technical details:
product brand name   SIRIUS
product designation   safety relays
Design of the product   for safe stoppage monitoring
protection class IP / of the housing   IP20
Protection class IP / of the terminal   IP20
Protection against electrical shock   finger-safe
Insulation voltage / rated value V 690
Ambient temperature    
  • during storage
°C -40 +75
  • during operating
°C -25 +60
Air pressure    
  • according to SN 31205
kPa 90 106
Relative humidity    
  • during operating phase
% 10 95
Installation altitude / at a height over sea level / maximum m 2,000
Resistance against vibration / according to IEC 60068-2-6   10 ... 55 Hz: 0.35 mm
Resistance against shock   8g / 10 ms
Impulse voltage resistance / rated value V 6,000
EMC emitted interference   IEC 61000-6-2, IEC 61000-6-3
Installation environment relating to EMC   This product is suitable for Class A environments only. It can cause undesired radio-frequency interference in residential environments. If this is the case, the user must take appropriate measures.
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  KT
  • according to DIN EN 61346-2
  F
Number of sensor inputs    
  • 1-channel or 2-channel
  1
Design of the cascading   none
Type of the safety-related wiring / of the inputs   measuring inputs
Product feature / transverse contact-secure   No
safety Integrated Level    
  • according to IEC 61508
  SIL3
SIL claim limit (for a subsystem) / according to EN 62061   3
[nicht versorgt: PMD_ABX011_001_000]    
  • according to ISO 13849-1
  e
Category / according to EN 954-1   4
Category / according to ISO 13849-1   4
Probability of dangerous failure per hour (PFHD) / with high demand rate / according to EN 62061 1/h 0.15E-8
T1 value / for proof test interval or service life / according to IEC 61508 a 20
Number of outputs / as contact-affected switching element    
  • as NC contact / for reporting function / instantaneous switching
  2
  • as NO contact / safety-related / instantaneous switching
  4
  • as NO contact / safety-related/ delayed switching
  0
Number of outputs / as contact-less semiconductor switching element    
  • safety-related
   
  • delayed switching
  0
  • non-delayed
  0
  • for reporting function
   
  • delayed switching
  0
  • non-delayed
  2
Stop category / according to DIN EN 60204-1   0
 
General technical details:
   
Design of the input    
  • cascading-entrance/operation-even switching
  No
  • reducing-entrance
  Yes
  • start-up entrance
  No
Design of the electrical connection / jumper socket   Yes
Operating cycles / maximum 1/h 1,200
Switching capacity current    
  • of semiconductor outputs
   
  • for signaling function / for DC-13 / at 24 V
A 0.1
  • of NO contacts of relay outputs
   
  • at DC-13
   
  • at 24 V
A 2
  • at AC-15
   
  • at 115 V
A 3
  • at 230 V
A 3
  • of NC contacts of relay outputs
   
  • at DC-13
   
  • at 24 V
A 2
  • at AC-15
   
  • at 115 V
A 2
  • at 230 V
A 2
Thermal current / of the contact-affected switching element / maximum A 5
Electrical operating cycles as operating time / typical   200,000
Mechanical operating cycles as operating time / typical   50,000,000
Design of the fuse link / for short-circuit protection of the NO contacts of the relay outputs / required   quick: 5 A
 
Control circuit:
   
Type of voltage / of the controlled supply voltage   AC
Control supply voltage frequency    
  • 1 / rated value
Hz 50
  • 2 / rated value
Hz 60
Control supply voltage / 1 / at 50 Hz / for AC / rated value V 230
Control supply voltage / 1 / at 60 Hz / for AC / rated value V 230
operating range factor control supply voltage rated value / of the magnet coil    
  • at 50 Hz
   
  • for AC
  0.8 1.1
  • at 60 Hz
   
  • for AC
 

Назад в раздел