SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), AC 115V, 22.5MM SCREW CONNECTION RC INSTANT.: 2NO, RC DELAYED: 0NO, MC: 0NC, AUTOSTART, BASIC UNIT, MAX. ACH. CAT. EN954-1: 3, ABB 1SAR501020R0004

Артикул: 3TK2824-1AJ20-0FB0
Производитель: Siemens


Наименование продукта
SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), AC 115V, 22.5MM SCREW CONNECTION RC INSTANT.: 2NO, RC DELAYED: 0NO, MC: 0NC, AUTOSTART, BASIC UNIT, MAX. ACH. CAT. EN954-1: 3, ABB 1SAR501020R0004
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1998-03-01
    Версия от 2011-08-28
 
(kein FDB-Text gefunden)
General technical details:
 
Design of the product for EMERGENCY-STOP units
Type of voltage  
  • of the operating voltage
AC/DC
  • of the controlled supply voltage
AC
Operating voltage  
  • 1 / for AC / rated value
230 V
  • 1 / for DC / rated value
24 V
  • 2 / for DC / rated value
115 V
  • 3 / for DC / rated value
230 V
Control supply voltage  
  • at 50 Hz / for AC / rated value / maximum
115 V
  • at 60 Hz / for AC / rated value / maximum
115 V
Number of outputs  
  • as contact-less semiconductor switching element
 
  • for reporting function / non-delayed
0
  • for reporting function / delayed switching
0
  • as contact-affected switching element
 
  • for reporting function / non-delayed
0
  • for reporting function / delayed switching
0
Breaking capacity current  
  • at AC-15 / at 230 V
6 A
  • at DC-13 / at 24 V
5 A
  • at DC-13 / at 115 V
0.2 A
  • at DC-13 / at 230 V
0.1 A
Product feature / transverse contact-secure No
   
Mechanical design:
 
Type of the safety-related wiring / of the inputs single-channel or single-channel and two-channel
Design of the electrical connection screw-type terminals
Design of the input  
  • Start-up entrance
Yes
  • Reducing-entrance
Yes
  • Cascading-entrance/operation-even switching
No
Design of the cascading none
Width 22.5 mm
Height 120 mm
Depth 120 mm
   
Product Function:
 
Protective door monitoring
Yes
monitored start-up
No
Automatic start
Yes
Step mat monitoring
No
Emergency-OFF function
No
Pressing control
No
Light grid monitoring
No
Light barrier monitoring
No
Laser scanner monitoring
No
Magnetic switch monitoring Normally closed contact-Normally closed contact
No
Magnetic switch monitoring Normally closed contact-Normally open contact
No
   
Approbationen/ Zertifikate:
 
Safety Integrated Level / acc. to IEC 61508 none
Security category / acc. to EN 954-1 2
 
letzte ?nderung:
08/24/2006


Назад в раздел