SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), AC 24V, 45.0MM, SCREW CONNECTION, RC INSTANT.: 3NO RC DELAYED: 0NO, MC: 2NC, AUTOSTART/MONIT. START BASIC UNIT, MAX. ACH. CAT. EN954-1: 4, ABB 1SAR501032R0002

Артикул: 3TK2825-1AB20-0FB0
Производитель: Siemens


Наименование продукта
SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), AC 24V, 45.0MM, SCREW CONNECTION, RC INSTANT.: 3NO RC DELAYED: 0NO, MC: 2NC, AUTOSTART/MONIT. START BASIC UNIT, MAX. ACH. CAT. EN954-1: 4, ABB 1SAR501032R0002
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
1998-03-01
    Версия от 2012-02-11
 
SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), AC 24V, 45.0MM, SCREW CONNECTION, RC INSTANT.: 3NO RC DELAYED: 0NO, MC: 2NC, AUTOSTART/MONIT. START BASIC UNIT, MAX. ACH. CAT. EN954-1: 4, ABB 1SAR501032R0002
 
General technical details:
product brand name   SIRIUS
product designation   safety relays
Design of the product   for EMERGENCY-STOP units
protection class IP / of the housing   IP20
Protection class IP / of the terminal   IP20
Protection against electrical shock   finger-safe
Insulation voltage / rated value V 300
Ambient temperature    
  • during storage
°C -40 +80
  • during operating
°C -25 +60
Air pressure    
  • according to SN 31205
kPa 90 106
Relative humidity    
  • during operating phase
% 10 95
Installation altitude / at a height over sea level / maximum m 2,000
Resistance against vibration / according to IEC 60068-2-6   5 ... 500 Hz: 0,075 mm
Resistance against shock   8g / 10 ms
Impulse voltage resistance / rated value V 4,000
EMC emitted interference   EN 60947-5-1
Item designation    
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  KT
  • according to DIN EN 61346-2
  F
Number of sensor inputs    
  • 1-channel or 2-channel
  1
Design of the cascading   none
Type of the safety-related wiring / of the inputs   single-channel and two-channel
Product feature / transverse contact-secure   Yes
safety Integrated Level    
  • according to IEC 61508
  SIL3
SIL claim limit (for a subsystem) / according to EN 62061   3
[nicht versorgt: PMD_ABX011_001_000]    
  • according to ISO 13849-1
  e
Category / according to EN 954-1   4
Category / according to ISO 13849-1   4
Probability of dangerous failure per hour (PFHD) / with high demand rate / according to EN 62061 1/h 0.15E-8
T1 value / for proof test interval or service life / according to IEC 61508 a 20
Number of outputs / as contact-affected switching element    
  • as NC contact / for reporting function / instantaneous switching
  2
  • as NO contact / safety-related / instantaneous switching
  3
  • as NO contact / safety-related/ delayed switching
  0
Number of outputs / as contact-less semiconductor switching element    
  • safety-related
   
  • delayed switching
  0
  • non-delayed
  0
  • for reporting function
   
  • delayed switching
  0
  • non-delayed
  0
Stop category / according to DIN EN 60204-1   0
 
General technical details:
   
Design of the input    
  • cascading-entrance/operation-even switching
  No
  • reducing-entrance
  Yes
  • start-up entrance
  Yes
Design of the electrical connection / jumper socket   Yes
Operating cycles / maximum 1/h 1,000
Switching capacity current    
  • of NO contacts of relay outputs
   
  • at DC-13
   
  • at 24 V
A 6
  • at 115 V
A 0.2
  • at 230 V
A 0.1
  • at AC-15
   
  • at 115 V
A 6
  • at 230 V
A 6
  • of NC contacts of relay outputs
   
  • at DC-13
   
  • at 24 V
A 6
  • at 115 V
A 0.2
  • at 230 V
A 0.1
  • at AC-15
   
  • at 115 V
A 6
  • at 230 V
A 6
Thermal current / of the contact-affected switching element / maximum A 6
Electrical operating cycles as operating time / typical   100,000
Mechanical operating cycles as operating time / typical   10,000,000
Design of the fuse link / for short-circuit protection of the NO contacts of the relay outputs / required   gL/gG: 6 A, or quick: 10 A
Resistance to direct current / of the cable / maximum ? 30
Cable length / between sensor and electronic evaluation device / with Cu 1.5 mm? and 150 nF/km / maximum m 1,000
Make time / with automatic start    
  • for AC / maximum
ms 150
Make time / with monitored start    
  • maximum
ms 25
Backslide delay time / at mains power cut    
  • maximum
ms 350
Recovery time / after opening of the safety circuits / typical ms 200
Recovery time / after mains power cut / typical s 0.5
Pulse duration    