| SIMATIC S7-400H, CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-400F/FH, 3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES 768 KB MEMORY (256 KB DATA/512 KB CODE) |
|
General information |
Hardware product version | 1 |
Firmware version | V4.5 |
Engineering with |
Programming package | STEP7 V 5.3 SP2 or higher with HW update |
CiR - Configuration in RUN |
CiR synchronization time, basic load | 150 ms |
CiR synchronization time, time per I/O slave | 40 µs |
Supply voltage |
24 V DC | No; Power supply via system power supply |
Input current |
from backplane bus 5 V DC, typ. | 1.2 A |
from backplane bus 5 V DC, max. | 1.5 A |
from backplane bus 24 V DC, max. | 150 mA; Per DP interface |
from interface 5 V DC, max. | 90 mA; At each DP interface |
Power losses |
Power loss, typ. | 5.5 W |
Backup battery |
Battery operation | |
Backup current, typ. | 190 µA; Valid up to 40°C |
Backup current, max. | 660 µA |
Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence |
Feeding of external backup voltage to CPU | 5 to 15 VDC |
Feeding of external backup voltage to CPU | 5 to 15 VDC |
Memory |
Work memory |
integrated | 768 kbyte |
integrated (for program) | 512 kbyte |
integrated (for data) | 256 kbyte |
expandable | No |
Load memory |
expandable FEPROM | Yes |
expandable FEPROM, max. | 64 Mbyte |
integrated RAM, max. | 256 kbyte |
expandable RAM | Yes |
expandable RAM, max. | 64 Mbyte |
Backup |
present | Yes |
with battery | Yes; all data |
without battery | No |
CPU processing times |
for bit operations, min. | 0.075 µs |
for word operations, min. | 0.075 µs |
for fixed point arithmetic, min. | 0.075 µs |
for floating point arithmetic, min. | 0.225 µs |
CPU-blocks |
DB |
Number, max. | 4095; Number range: 1 to 4095 |
Size, max. | 64 kbyte |
FB |
Number, max. | 2048; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
FC |
Number, max. | 2048; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
OB |
Size, max. | 64 kbyte |
Number of time alarm OBs | 4 |
Number of delay alarm OBs | 4 |
Number of time interrupt OBs | 4 |
Number of process alarm OBs | 4 |
Nesting depth |
per priority class | 24 |
additional within an error OB | 1 |
Counters, timers and their retentivity |
S7 counter |
Number | 2048 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 2047 |
preset | Z 0 to Z 7 |
Counting range |
lower limit | 0 |
upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 2048 |
Retentivity |
adjustable | Yes |
lower limit | 0 |
upper limit | 2047 |
preset | No times retentive |
Time range |
lower limit | 10 ms |
upper limit | 9990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
retentive data area, total | Total working and load memory (with backup battery) |
Flag |
Number, max. | 8 kbyte |
Retentivity available | Yes |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; (in 1 memory byte) |
Data blocks |
Number, max. | 4095; Number range: 1 to 4095 |
Size, max. | 64 kbyte |
Local data |
adjustable, max. | 16 kbyte |
preset | 8 kbyte |
Address area |
I/O address area |
Inputs | 8 kbyte |
Outputs | 8 kbyte |
of which, distributed |
MPI/DP interface, inputs | 2 kbyte |
MPI/DP interface, outputs | 2 kbyte |
Process image |
Inputs, adjustable | 8 kbyte |
Outputs, adjustable | 8 kbyte |
Inputs, default | 256 byte |
Outputs, default | 256 byte |
consistent data, max. | 244 byte |
Access to consistent data in process image | Yes |
Subprocess images |
Number of subprocess images, max. | 15 |
Digital channels |
Inputs | 65536 |
Outputs |
|