LDA2423-T-AD-TVL T UNIT 1,2 BRANCH ABOVE OFFSET UNIT

Артикул: BVP:000115
Производитель: Siemens


Наименование продукта
LDA2423-T-AD-TVL T UNIT 1,2 BRANCH ABOVE OFFSET UNIT
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01
LDA2423-T-AD-TVL T UNIT 1,2 BRANCH ABOVE OFFSET UNIT
 
General technical data:
Configuration of the busbars   L1,L2,L3,PEN
Type of mounting   ceiling / wall
RAL color number   RAL 7035
Color   light grey
Number of conductors   4
Conductor cross section / of the (PE)N mm? 706
Product component / fire sealing   No
Material / of the busbar   aluminium
Number of conductors / without PE   4
Length of the AY leg / of the busbar box junction unit m 0.3
Length of the AX leg / of the busbar box junction unit m 0.5
Resistance against the impulse current / at 690 V / rated value kA 154
Insulation voltage    
  • for DC / rated value
V 1,200
  • for AC / rated value
V 1,000
Operating frequency / rated value    
  • minimum
Hz 16.7
  • maximum
Hz 60
Length of the X-dimension / of the busbar box junction unit    
  • minimum
m 0.58
  • maximum
m 0.58
Length of the Y-dimension / of the busbar box junction unit    
  • minimum
m 0.62
  • maximum
m 0.62
Length of the Z-dimension / of the busbar box junction unit    
  • minimum
m 0
  • maximum
m 0
Short-time current resistance (Icw) / at 690 V    
  • limited to 0.1 s / rated value
kA 70
  • limited to 1 s / rated value
kA 55
Operating voltage    
  • at 50 Hz / at AC / rated value / maximum
V 1,000
  • at 60 Hz / at AC / rated value / maximum
V 1,000
Operating current    
  • for circuit 1
   
  • at 50 Hz / for AC / for vertical busbar box / rated value
A 1,100
  • at 60 Hz / for AC / for vertical busbar box / rated value
A 1,100
  • at 50 Hz / for AC / rated value / maximum
A 1,250
  • at 60 Hz / for AC / rated value / maximum
A 1,250
  • at 50 Hz / for AC / for horizontal busbar box with flat busbars / rated value / maximum
A 750
  • at 60 Hz / for AC / for horizontal busbar box with flat busbars / rated value / maximum
A 750
product designation   T unit (junction unit) for LD busbar trunking system
Protection class IP   IP34
Product type designation   LDA2423-T-AD-TVL
Height mm 480
Width mm 500
 
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Global Industry Mall (Online ordering system)
http://www.siemens.com/lowvoltage/mall
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/BVP:000115/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=BVP:000115
 
last change:
Aug 19, 2011


Назад в раздел