| LXA0951-FLV-X*/Y* FLANGED END |
|
General technical details: |
product designation | | feeder unit for LX busbar trunking system |
Product type designation | | LXA0951-FLV-X*/Y* |
Operating current / for circuit 1 / at 50 Hz / for AC / rated value / maximum | A | 4,000 |
Resistance against the impulse current / at 1000 V / rated value | kA | 255 |
Short-time current resistance (Icw) / at 1000 V / limited to 1 s / rated value | kA | 140 |
Operating frequency / rated value / minimum | Hz | 50 |
Operating frequency / rated value / maximum | Hz | 50 |
Operating voltage / at 50 Hz / at AC / rated value / maximum | V | 690 |
Insulation voltage / for AC / rated value | V | 690 |
Insulation voltage / for DC / rated value | V | 800 |
Number of circuits / in one busbar box | | 1 |
Number of poles | | 5 |
|
Mechanical design: |
Position / of the infeed / on the busbar box | | entry, centre |
Type of mounting | | ceiling / wall |
Material / of the busbar | | aluminium |
Length of the X-dimension / of the busbar box junction unit / minimum | m | 0.8 |
Length of the X-dimension / of the busbar box junction unit / maximum | m | 1.15 |
Length of the Y-dimension / of the busbar box junction unit / minimum | m | 0.8 |
Length of the Y-dimension / of the busbar box junction unit / maximum | m | 1.15 |
Length | m | 1.35 |
Width | mm | 400 |
Height | mm | 1,230 |
Color | | light grey |
|
Ambient conditions: |
Protection class IP | | IP00 |
|
Further information: |
Information- and Downloadcenter (Catalogs, Brochures,…) http://www.siemens.com/lowvoltage/catalogs |
Global Industry Mall (Online ordering system) http://www.siemens.com/lowvoltage/mall |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/BVP:660767/all |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=BVP:660767 |
|
|
|
last change: | Aug 26, 2011 |