MAIN CONTROL SWITCH 4-POLE IU=25, P/AC-23A AT 400V=9,5KW 1NO+1 NC, FRONT MOUNTING FOUR-HOLE MOUNTING ROTARY ACTUATOR BLACK

Артикул: 3LD2103-2EP51
Производитель: Siemens


Наименование продукта
MAIN CONTROL SWITCH 4-POLE IU=25, P/AC-23A AT 400V=9,5KW 1NO+1 NC, FRONT MOUNTING FOUR-HOLE MOUNTING ROTARY ACTUATOR BLACK
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2001-01-01
Similar to image
MAIN CONTROL SWITCH 4-POLE IU=25, P/AC-23A AT 400V=9,5KW 1NO+1 NC, FRONT MOUNTING FOUR-HOLE MOUNTING ROTARY ACTUATOR BLACK
 
General technical details:
Product brand name   SENTRON
product designation   main and EMERGENCY-OFF switches
Type from device   fixed mounting
Design of the operating mechanism   rotary actuator, black
Protection class IP   IP65
Number of poles   4
Acceptability for application    
  • switch disconnector
  Yes
  • main switch
  Yes
  • safety cut-out switch
  Yes
  • emergency stop switch
  No
  • maintenance/repair switch
  Yes
Product equipment / interlock   Yes
Type of the driving mechanism / motor drive   No
Product extension / optional    
  • motor drive
  No
  • voltage trigger
  No
Ambient temperature / during operating °C -25 55
Insulation voltage / rated value V 690
Impulse voltage resistance / rated value V 6,000
Active power loss / per conductor / typical W 1.1
Mechanical operating cycles as operating time / of the main contacts / typical   100,000
Protection against electrical shock   finger-safe
Item designation / according to DIN EN 61346-2   S
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750   S
 
Main circuit:
   
Continuous current / rated value A 25
Operating current / at AC-21 / rated value A 25
Short-time current resistance (Icw) / at 690 V / limited to 1 s / rated value A 640
Operating frequency Hz 50 60
Operating voltage / at 50/60 Hz / for AC / rated value V 690
Service power / at AC-3    
  • at 400 V / rated value
kW 7.5
  • at 690 V / rated value
kW 7.5
Service power / at AC-23a    
  • at 400 V / rated value
kW 9.5
  • at 690 V / rated value
kW 9.5
Operating cycles / maximum 1/h 50
 
Auxiliary circuit:
   
Number of NC contacts / for auxiliary contacts   1
Number of NO contacts / for auxiliary contacts   1
Number of change-over switches / for auxiliary contacts   0
Continuous current / of the auxiliary contact / rated value A 10
Operating voltage / of the auxiliary contacts / for AC / maximum V 500
Insulation voltage / of the auxiliary switch / rated value V 500
 
Short-circuit:
   
Design of the fuse link / for short-circuit protection of the main circuit / necessary   fuse gL/gG: 25 A
Design of the fuse link / for short-circuit protection of the auxiliary switch / required   fuse gL/gG: 10 A
 
Installation/mounting/dimensions:
   
Type of mounting   front mounting
  • front mounting
  Yes
  • front mounting with central fixation
  No
  • front mounting with 4-hole fixation
  Yes
  • series installation
  Yes
  • Rail installation
  No
Width mm 67
Height mm 84
Depth mm 92.5
 
Connection type:
Design of the electrical connection / for main current circuit   connection terminals
Design of the electrical connection / for auxiliary contact   connection terminals
Type of the connectable conductor cross-section / for main contacts    
  • solid
  1.5 ... 16 mm2
  • finely stranded / with conductor end processing
  10 mm2
  • stranded
  1.5 ... 16 mm2
Type of connectable conductor cross section / for auxiliary contacts    
  • solid
  2x (0.75 ... 2.5 mm2), 1x 4 mm2
  • finely stranded / with conductor end processing
  2x (0.75 ... 1.5 mm2), 1x 2.5 mm2
  • stranded
  2x (0.75 ... 2.5 mm2), 1x 4 mm2
 
Certificates/approvals:
Verification of suitability   CSA / UL / CCC / GL / LRS / DNV / PRS
Conductor cross section that can be connected / for main contacts / solid / minimum mm? 1.5
Conductor cross section that can be connected / for main contacts / solid / maximum mm? 16
Conductor cross section that can be connected / for main contacts / stranded / minimum mm? 1.5
Conductor cross section that can be connected / for main contacts / stranded / maximum mm? 16
Conductor cross-section that can be connected / for main contacts / stranded wire / with conductor end processing / maximum mm? 10
Conductor cross section that can be connected / for auxiliary contacts / solid / minimum mm? 0.75
Conductor cross section that can be connected / for auxiliary contacts / solid / maximum mm? 4
Conductor cross-section that can be connected / for auxiliary contact / stranded wire / with conductor end processing / minimum mm? 0.75
Conductor cross-section that can be connected / for auxiliary contact / stranded wire / with conductor end processing / maximum mm? 2.5
Conductor cross section that can be connected / for auxiliary contacts / stranded / min. mm? 0.75
Conductor cross section that can be connected / for auxiliary contacts / stranded / max. mm? 4
 
Certificates/approvals:
General Product Approval Test Certificates
 
last change:
Aug 25, 2011