AS-Interface sensor/actuator module | VAA-2EA-G2-ZE0/E0

Артикул: VAA-2EA-G2-ZE0/E0
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • Connection via flat cable
  • Cable piercing technique
  • Function display for bus, inputs and outputs
  • LED for monitoring communication
  • Variable flat cable design
  • Addressing jack
  • Display of address "0"/Communication error
  • Display of "external auxiliary power"
  • PE connection possible
  • Power supply of inputs from the module

Datasheet as PDF in following languages:


Technical Data: VAA-2EA-G2-ZE0/E0

Product Description
G2 flat module
2 inputs/2 outputs
General specifications
Slave typeStandard slave
Indicators/operating means
LED CONFIG ERRcommunication error / address is 0; LED red
LED U AS-iAS-Interface voltage/sensor overload; LED green/LED red
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA (without sensors) / max. 180 mA
Protection classIII
Input
Number/Type2 inputs for 2- or 3-wire sensors (NPN), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity≤ 150 mA (TB ≤ 40 В°C),
≤ 120 mA (TB ≤ 60 В°C), short-circuit protected
Input current≤ 8 mA (limited internally)
Switching point
0 (unattenuated)≤ 1.5 mA
1 (attenuated)≥ 4.5 mA
Output
Number/Type2 electronic outputs, NPN
Supplyfrom external auxiliary voltage UAUX
Current0.5 A per output
Voltage≥ (UAUX - 0.5 V)
Programming instructions
ProfileS-3.F
IO code3
ID codeF
Data bits (function via AS-Interface) input output
D0 IN1 -
D1 IN2 -
D2 - OUT3
D3 - OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring
P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP67 according to EN 60529
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Mass100 g
MountingMounting base


Назад в раздел