Product Description |
G6 compact module 2 inputs (PNP) and 2 electronic outputs |
General specifications |
Slave type | Standard slave |
AS-Interface specification | V2.0 |
Required master specification | ≥ V2.0 |
UL File Number | E87056 |
Indicators/operating means |
LED UAUX | ext. auxiliary voltage UAUX ; LED green |
LED AS-i | AS-Interface voltage; LED green |
LED IN | switching state (input); 2 LED yellow |
LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications |
Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 40 mA (without sensors) / max. 240 mA |
Protection class | III |
Input |
Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 200 mA (TB ≤ 40 В°C), ≤ 150 mA (TB ≤ 60 В°C), short-circuit protected |
Input current | ≤ 8 mA (limited internally) |
Switching point | |
| 0 (unattenuated) | ≤ 1.5 mA |
| 1 (attenuated) | ≥ 4.5 mA |
Output |
Number/Type | 2 electronic outputs, PNP |
Supply | from external auxiliary voltage UAUX |
Current | 0.5 A per output, 1 A total (TB ≤ 40 В°C), 0.4 A per output, 0.8 A total (TB ≤ 60 В°C) |
Voltage | ≥ (UAUX - 0.5 V) |
Programming instructions |
Profile | S-3.0 |
IO code | 3 |
ID code | 0 |
Data bits (function via AS-Interface) | input output |
| D0 | IN1 - |
| D1 | IN2 - |
| D2 | - OUT1 |
| D3 | - OUT2 |
Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Compliance with standards and directives |
Directive conformity | observe notices on the certificate of conformity. |
Standard conformity | |
| Noise immunity | EN 61000-6-2:2001 |
| Emitted interference | EN 61000-6-4:2001 |
| AS-Interface | EN 50295:1999 |
| Input | EN 61131-2 |
| Protection degree | EN 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Storage temperature | -20 ... 85 В°C (-4 ... 185 В°F) |
Mechanical specifications |
Protection degree | IP67 |
Connection | AS-Interface and auxiliary voltage: M12 x 1 round connector sensors/actuators: M8 x 1 round connector |
Mounting | screw mounting |