Product Description |
G2 flat module for motor starter 2 inputs/2 electronic outputs |
General specifications |
Slave type | Standard slave |
AS-Interface specification | V2.1 |
Required master specification | ≥ V2.0 |
UL File Number | E87056 |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
LED PWR | AS-Interface voltage; LED green |
LED IN | switching state (input); 2 LED yellow |
LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 30 mA (without sensors) / max. 180 mA |
Protection class | III |
Input |
Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 150 mA (TB ≤ 40 В°C), ≤ 120 mA (TB ≤ 60 В°C), short-circuit protected |
Input current | ≤ 8 mA (limited internally) |
Switching point | |
| 0 (unattenuated) | ≤ 1.5 mA |
| 1 (attenuated) | ≥ 4.5 mA |
Output |
Number/Type | 2 electronic outputs, PNP |
Supply | from AS-Interface |
Current | limited by the current loading capacity of the module |
Programming instructions |
Profile | S-3.F |
IO code | 3 |
ID code | F |
Data bits (function via AS-Interface) | input output |
| D0 | IN1 - |
| D1 | IN2 - |
| D2 | - OUT3 |
| D3 | - OUT4 |
Parameter bits (programmable via AS-i) | function |
| P0 | communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Compliance with standards and directives |
Directive conformity | |
| EMC Directive 89/336/EEC | EN 61000-6-2:2001, EN 61000-6-4:2001, EN 50295:1999 |
Standard conformity | |
| Noise immunity | EN 61000-6-2:2001 |
| Emitted interference | EN 61000-6-4:2001 |
| AS-Interface | EN 50295:1999 |
| Input | EN 61131-2 |
| Protection degree | EN 60529 |
Ambient conditions |
Ambient temperature | -25 ... 60 В°C (-13 ... 140 В°F) |
Storage temperature | -25 ... 85 В°C (-13 ... 185 В°F) |
Mechanical specifications |
Protection degree | IP67 |
Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
Mass | 100 g |
Mounting | Mounting base |