Zener Barrier | SB0041

Артикул: SB0041
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@sm-industry.ru
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@sm-industry.ru

  • 2-channel
  • DC version, positive polarity
  • Working voltage 7 V at 2 µA
  • Series resistance max. 2039 Ω
  • Fuse rating 80 mA
  • Terminal Base or Termination Board mounting, pluggable
  • Replaceable fuse

Datasheet as PDF in following languages:


Technical Data: SB0041

General specifications
TypeDC version, positive polarity
Electrical specifications
Nominal resistancewithout back-up fuse 2008.5 Ω , with back-up fuse 2016 Ω
Series resistancewithout back-up fuse max. 2030.5 Ω , with back-up fuse max. 2039 Ω
Fuse ratinginternal fuse 80 mA , back-up fuse (fast acting) 80 mA
Hazardous area connection
Connectionterminals 13; 23
Safe area connection
Connectionterminals 11; 21
Working voltage7 V at 2 µA
Conformity
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-40 ... 80 В°C (-40 ... 176 В°F)
Mechanical specifications
Protection degreeIP20 (installed on Terminal Base or Termination Board)
Connectionwiring via Terminal Base or Termination Board
Massapprox. 70 g
Dimensions9.7 x 70.4 x 68.2 mm (0.4 x 2.8 x 2.7 in)
MountingTerminal Base or Termination Board mounting on 35 mm DIN rail acc. to DIN EN 60715
Data for application in connection with Ex-areas
EC-Type Examination CertificateTГњV 99 ATEX 1449 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1) G [Ex ia] IIC
Ex-Hexagon II (1) D [Ex iaD]
Directive conformity
Directive 94/9/ECEN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006