Termination Board for Honeywell Experion Series C GI/IO | SC-GPCS-UNI16-PF

Артикул: SC-GPCS-UNI16-PF
Производитель: Pepperl-Fuchs



  • System Board for Honeywell Experion PKS, Series C
  • For 16-/32-channel cards CC-TDIL01/11, CC-TDOB01/11, CC-TAIX01/11 and CC-TAOX01/11
  • For 16 modules
  • Recommended modules: HiC2821 (DI), HiC2871 (DO), HiC2025 (AI), HiC2031 (AO)
  • Recommended system cable: CA-HWC300-AIO-DIO-*M
  • 24 V DC supply
  • Hazardous area: pluggable screw terminals, blue
  • Safe area: Sub-D connector (male), 37-pin

Datasheet as PDF in following languages:


Technical Data: SC-GPCS-UNI16-PF

Supply
Connectionterminal block TB3 (1-, 2+; 3-, 4+)
Rated voltage24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple≤ 10 %
Fusing4 A
Power loss≤ 500 mW , without modules
Reverse polarity protectionyes
Redundancy
SupplyRedundancy available. The supply for the modules is decoupled, monitored and fused.
Output
Connectionterminal block TB4 (1, 2), error message output, NO contact
Contact loadingmax. 30 V AC/40 V DC, 2 A resistive load
Indicators/settings
Display elementsLEDs PWR ON (power supply)
- LED power supply I, green LED
- LED power supply II, green LED
LED Fault (fault indication), red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Storage temperature-40 ... 70 В°C (-40 ... 158 В°F)
Mechanical specifications
Protection degreeIP20
Connectionhazardous area connection (field side): plugable screw terminals, blue
safe area connection (control side): 37-pin Sub-D connector (male)
Materialhousing: polycarbonate, 30 % fiberglass reinforced
Massapprox. 900 g
Dimensions273 x 155 x 153 mm (L x W x H) , height including module assembly
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateCESI 06 ATEX 022 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [Ex ia] IIC; [Ex iaD] 20
Ex-Hexagon I (M1) [Ex ia] I
Safe area
Maximum safe voltage250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuitsafe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 , EN 61241-0: 2006, EN 61241-11: 2006 , EN 50303:2000
International approvals
UL approval
Control drawing116-0327
IECEx approvalIECEx CES 06.0003
Approved for[Zone 0] [Ex ia] IIC, [Ex ia] I