Binary input | RSD-BI-Ex16

Артикул: RSD-BI-Ex16
Производитель: Pepperl-Fuchs



  • 16-channel
  • Inputs EEx ia IIC
  • Device installation in Zone 1, Zone 2, or Zone 22
  • Module can be exchanged under voltage in Zone 1 (hot swap)
  • Inputs according to NAMUR in acc. with EN 60947-5-6
  • Lead breakage (LB) and short-circuit (SC) monitoring of the inputs
  • EMC acc. to NAMUR NE 21

Datasheet as PDF in following languages:


Technical Data: RSD-BI-Ex16

Supply
Connectionterminals 34, 50 V+; 35, 51 V-
Rated voltage8.88 ... 9.5 V
Power loss2.8 W
Power consumption2.8 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer specific bus
Cycle time1.6 ms
Input
Connectionterminals 0+, 1-; 2+, 3-; 4+, 5-; 6+, 7-; 8+, 9-; 10+, 11-; 12+, 13-; 14+, 15-; 17+, 18-; 19+, 20-; 21+, 22-; 23+, 24-; 25+, 26-; 27+, 28-; 29+, 30-; 31+, 32-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 25 µs / min. 25 µs
Line fault detectionbreakage I ≤ 0,15 mA; short-circuit I > 6 mA
Transfer characteristics
Switching frequencymax. 1 kHz
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007, EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Climatic conditionsIEC 60721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeTerminals
Core cross-sectionmax. 2.5 mm2
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 235 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 98 ATEX 003 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)2G Ex ib[ia] IIC T4
Ex-Hexagon II (1)D [Ex iaD]
Supplyonly in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34
Input
Voltage14.5 V
Current15 mA
Power40 mW
External capacitance300 nF
External inductance2 mH
L/R-ratio0.65 mH/Ω
Internal buscustomer specific
Statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3D IP54 T 90В°C
Electrical isolation
Input/inputno electrical isolation
Input/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Input/Internal Bussafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Internal bus/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V