ControlNet copper/LWL adapter | RSD-CFA-Ex.CN

Артикул: RSD-CFA-Ex.CN
Производитель: Pepperl-Fuchs



  • Converts the ControlNet coaxial signals into TTL signals for the ControlNet LWL coupler
  • EEx ia IIC
  • Device installation in Zone 1, Zone 2, or Zone 22
  • Transfer rate 5 MBits/s
  • Connection of up to two LWL couplers, each with two bi-directional LWL transfer routes
  • 1 power supply channel for 1 copper/fiber optic adapter

Datasheet as PDF in following languages:


Technical Data: RSD-CFA-Ex.CN

Supply
Connectionterminals V+, V-
Rated voltage8.88 ... 9.5 V
Power loss8 W
Power consumption8.5 W
Internal bus
ConnectionTTL bus
Interfacemanufacturer specific bus
Max. number of fiber optic couplers2
External bus
ConnectionBNC connection
InterfaceControlNet international version 1.5, intrinsically safe
Transfer rate5 MBit/s
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Explosion protection
Directive 94/9/ECEN 60079-0: 2006, EN 60079-11: 2007 , EN 60079-26:2007
Standard conformity
Insulation coordinationEN 50178
Electrical isolationEN 60079-11:2007
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Climatic conditionsDIN IEC 721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 70 В°C (-4 ... 158 В°F)
Storage temperature-20 ... 100 В°C (-4 ... 212 В°F)
Relative humidity95 % non-condensing
Shock resistance15 g peak, 11 ms period
Vibration resistance2 g , 10 ... 500 Hz according to IEC 60068-2-6
Damaging gasacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeterminals, BNC connection
Core cross-sectionmax. 2.5 mm2
Protection degreeIP20, for on-site installation a separate housing is required with a minimum of IP54
Massapprox. 320 g
MountingDIN rail mounting
Data for application in connection with Ex-areas
EC-Type Examination CertificateDMT 99 ATEX 010 X , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)2G EEx ia/ib IIB/IIC
Temperature classT4
Voltage Ui9.5 V
Current Ii1 A
Power Pi9.5 W
Supplyonly in connection with the power units RSD2-PSD2-Ex4.34, RSA6-PSD-Ex4.34
External bus
Voltage5.4 V
Current201 mA
Internal buscustomer specific
Statement of conformity
Group, category, type of protection, temperature classEx-Hexagon II 3D IP54 T 90В°C
Electrical isolation
Internal/external busno electrical isolation
Internal bus/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
External bus/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V


Назад в раздел